P1400+ TEMPERATURE CONTROLLER INSTRUCTION MANUAL E-104 PN 197252 REVISION 1-09
TABLE OF CONTENTS TABLE OF CONTENTS .....................................................................................................................iii SECTION 1: INTRODUCTION ............................................................................................................1 1.1 General ................................................................................................................................................. 1 SECTION 2: INSTALLATION.....................................
SECTION5: POWERING UP .............................................................................................................24 5.1 Powering Up Procedure......................................................................................................................24 5.2 Overview of Front Panel .....................................................................................................................24 5.3 Displays .......................................................................
SECTION 11: ASCII COMMUNICATIONS ........................................................................................64 11.1 Physical Layer .................................................................................................................................. 64 11.2 Device Addressing............................................................................................................................ 64 11.3 Session Layer .................................................................
How to use this manual This manual is structured to give easy access to the information required for all aspects of the installation and use and of the products: Section 1: Introduction - A brief description of the product range. Section 2: Installation - Unpacking, installing and panel mounting instructions. Section 3: Plug-in Options - Installation of the plug-in option modules.
SECTION 1: INTRODUCTION 1.1 General These instruments are microprocessor based process controllers. They can measure, display or control process variables such as temperature, pressure, flow and level from a variety of inputs. The operating voltage is either 100-240V at 50/60 Hz or 24V-48V AC/DC depending on the model purchased. EEPROM technology protects against data or configuration loss during power outages.
SECTION 2: INSTALLATION 2.1 Unpacking 1. Remove the product from its packing. Retain the packing for future use, in case it is necessary to transport the instrument to a different site or to return it to the supplier for repair/testing. 2. The instrument is supplied with a panel gasket and push fit fixing strap. A single sheet concise manual is also supplied in one or more languages. Examine the delivered items for damage or defects. If any are found, contact your supplier immediately. 2.
2.3 Panel Cut-outs The mounting panel must be rigid and may be up to 6.0mm (0.25 inches) thick. The cut-outs required for the instruments are shown below. 90mm +0.5 –0.0 (3.62” +.020 -.000) 90mm +0.5 –0.0 (3.62” +.020 -.000) Figure 2. Panel cut-out size 2.4 Panel-Mounting CAUTION: Ensure the inside of the panel is with the instruments operating temperature and that there is adequate air flow to prevent overheating.
Once the instrument is installed in its mounting panel, it may be subsequently removed from it’s housing, if necessary, as described in the Fitting and Removing Option Modules section. Instruments may be mounted side-by-side in a multiple installation, but instrument to panel moisture and dust sealing will be compromised. The cut-out width (for n instruments) is shown below. 1 /4 - DIN Instruments: (96n - 4) mm or (3.78n - 0.
SECTION 3: PLUG-IN OPTIONS 3.1 Options Modules and Functions A range of plug-in option modules is available to add additional input, output and communication functions to the instruments in the range. These modules can be either pre-installed at the time of manufacture, or retrofitted in the field. The modules are installed between the instruments main circuit boards into the four option slots. These are designated as Slots 1, 2, 3, A & B. Installation is detailed below.
Table 1.
3.3 Preparing to Install or Remove Options Modules CAUTION: Before removing the instrument from it’s housing, ensure that all power has been removed from the rear terminals. 1. Remove the instrument from its housing by gripping the side edges of the front panel (there is a finger grip on each edge) and pull the instrument forwards. This will release the instrument from the rear connectors in the housing and will give access to the PCBs. 2.
CAUTION: Take care not to put undue stress on the ribbon cable attaching the display and CPU boards. 2. Remove or fit the modules into the Option slots as required. The location of the connectors is shown below. Tongues on each option module locate into a slots cut into the main boards, opposite each of the connectors. Option Slot B Connectors PL2A, PL2B & PL2C Option Slot 2 Connector PL4A Option Slot 1 Connectors PL7 & PL8 Option Slot A Connectors PL5 & PL6 Option Slot 3 Connectors PL4B 1 Figure 6.
3.5 Replacing the Instrument in its Housing With the required option modules correctly located into their respective positions the instrument can be replaced into its housing as follows: 1. If required, move the CPU and PSU boards back together, taking care to locate the option module tongues into the slots in the board opposite. Hold the main boards together while relocating them back into the mounting struts on the front panel. 2.
SECTION 4: WIRING INSTRUCTIONS Electrical noise is a phenomenon typical of industrial environments. As with any instrumentation, these guidelines should be followed to minimize the effect of noise. 4.1 Installation Considerations Ignition transformers, arc welders, mechanical contact relays and solenoids are all common sources of electrical noise in an industrial environment and therefore the following guidelines MUST be followed. 1.
CAUTION: The only wires that should run together are those of the same category. If any wires need to run parallel with any other lines, maintain a minimum space of 150mm between them. If wires MUST cross each other, ensure they do so at 90 degrees to minimise interference. 4.4 Use of Shielded Cable All analogue signals must use shielded cable. This will help eliminate electrical noise induction on the wires.
Contacts:- Arcing may occur across contacts when they open and close. This results in electrical noise as well as damage to the contacts. Connecting a properly sized RC network can eliminate this arc. For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor (1000 volts) is recommended. For circuits from 3 to 5 amps, connect two of these in parallel. Figure 8. Contact noise suppression 4.
4.7 Thermocouple Wire Identification Chart The different thermocouple types are identified by their wires colour, and where possible, the outer insulation as well. There are several standards in use throughout the world. The table below shows the wire and sheath colours used for most thermocouple types. The format used in this table is: + Wire - Wire Sheath common Table 2.
WARNING: CHECK THE INFORMATION LABEL ON THE CASE TO DETERMINE THE CORRECT VOLTAGE BEFORE CONNECTING TO A LIVE SUPPLY. Note: The wiring diagram below shows all possible combinations. The actual connections required depend upon the features available on the model and the modules and options fitted. 1 Figure 9.
4.9 Power Connections - Mains Powered Instruments Mains powered instruments operate from a 100 to 240V (±10%) 50/60Hz supply. Power consumption is 7.5VA. Connect the line voltage (live and neutral) as illustrated via a two-pole isolating switch (preferably located near the equipment) and a 1amp anti-surge fuse.
WARNING: CHECK THE INFORMATION LABEL ON THE CASE TO DETERMINE THE CORRECT VOLTAGE BEFORE CONNECTING TO A LIVE SUPPLY. 4.11 Universal Input Connections - Thermocouple (T/C) Use only the correct thermocouple wire or compensating cable from the probe to the instrument terminals avoiding joints in the cable if possible. Failure to use the correct wire type will lead to inaccurate readings. Ensure correct polarity of the wires by cross-referencing the colours with a thermocouple reference table.
4.13 Universal Input Connections - Linear Volt, mV or mA input Linear DC voltage, millivolt or milliamp input connections are made as illustrated. Carefully observe the polarity of the connections. 4 + 3 _ 2 + _ mA mV/V 1 Figure 14. DC Volt, mV & mA Input Connections 4.14 Option Slot 1 Relay Output Module If option slot 1 is fitted with a relay output module, make connections as illustrated. The relay contacts are rated at 2 amps resistive, 240 VAC (120V max for direct Valve Motor control).
Option Slot 1 - SSR Driver Output Module If option slot 1 is fitted with an SSR driver output module, make connections as illustrated. The solidstate relay driver is a 0-10V DC signal, load impedance must be no less than 500 ohms. SSR driver outputs are not isolated from the signal input or other SSR driver outputs. 20 21 ∼ Figure 16. Option Slot 1 - SSR Driver Module Connections Option Slot 1 - Triac Output Module If option slot 1 is fitted with a Triac output module, make connections as shown.
4.15 Option Slot 2 Option Slot 2 - Relay Output Module If option slot 2 is fitted with a relay output module, make connections as illustrated. The relay contacts are rated at 2 amps resistive, 240 VAC (120V max for direct Valve Motor control). 22 N/C 23 COM 24 N/O Figure 19. Option Slot 2 - Relay Module Connections Option Slot 2 - SSR Driver Output Module If option slot 2 is fitted with an SSR driver output module, make connections as illustrated.
WARNING: THIS MODULE MUST NOT BE FITTED INTO OPTION SLOT 3. Option Slot 2 - Linear Voltage or mADC Output module If option slot 2 is fitted with a DC linear output module, make connections as illustrated. 22 _ 23 24 + Figure 22. Option Slot 2 - Linear Voltage & mADC module Connections 4.16 Option Slot 3 Option Slot 3 - Relay Output Module If option slot 3 is fitted with a relay output module, make connections as illustrated.
Option Slot 3 - SSR Driver Output Module If option slot 3 is fitted with an SSR driver output module, make connections as illustrated. The solidstate relay driver is a 0-10V DC signal; load impedance must be no less than 500 ohms. SSR driver outputs are not isolated from the signal input or other SSR driver outputs. _ 10 11 12 + Figure 24.
4.17 Option Slot A Option Slot A Connections - RS485 Serial Communications Module If option slot A is fitted with the RS485 serial communication module, connections are as illustrated. Carefully observe the polarity of the A (Rx/Tx +ve) and B (Rx/Tx -ve) connections. 16 A 17 B 18 COM RS485 Figure 27.
4.18 Option Slot B Option Slot B Connections – Heater Current Input Module If the heater current measurement feature is available, connections from the secondary winding of the current transformer are as illustrated below. 7 6 ∼ CT Secondary Figure 30. Option Slot B – Heater Current Input Connections Option Slot B Connections – Digital Input 2 (Full Auxiliary Module) If option slot B is fitted with the Full Auxiliary input module (see below), a secondary digital input is also provided.
SECTION 5: POWERING UP WARNING: ENSURE SAFE WIRING PRACTICES ARE FOLLOWED The instrument must be powered from a supply according to the wiring label on the side of the unit. The supply will be either 100 to 240V AC, or 24/48V AC/DC powered. Check carefully the supply voltage and connections before applying power. CAUTION: When powering up for the first time, disconnect the output connections. 5.
5.3 Displays Controllers are provided with a dual line display and LED indicators for mode, automatic tune, alarm and output status. The upper display shows the process variable value during normal operation, while the lower display shows the Setpoint value. See the preceding diagram - Typical front panel and keys. 5.4 Keypad Each instrument in the range has four switches, which are used to navigate through the user menus and make adjustment to the parameter values.
SECTION 6: MESSAGES AND ERROR INDICATIONS The following displays are shown when an error occurs or a hardware change is detected. Table 4. Error/Faults conditions Error/Faults Conditions Upper display Configuration & Setup is required. Seen at first turn on or if hardware configuration changed. Press to enter Configuration Mode, next press or to enter the unlock code number, then press to proceed.
SECTION 7: INSTRUMENT OPERATION MODES 7.1 Select Mode This mode is used to gain entry to each of the modes available in the instrument. Entry into the Select Mode Hold down and press in any mode to force the unit to enter Select Mode. Navigating in Select Mode Once in Select Mode, press or to select the required mode, then press to enter the chosen mode. To prevent unauthorised entry to Configuration, Setup and Automatic Tuning modes, an unlock code is required.
Table 6. Lock Code – Entry and Default Values Description Default values are: Automatic Tune Mode = 0 Set-up mode = 10 Configuration Mode = 20. Upper/Main Display 0 Lower Display ULoc 7.2 Automatic Tune Mode Automatic Tune Mode is selected when it is desired to use the Pre-tune and Self-tune facilities on a controller to assist the user in setting up Proportional band, Integral and Derivative parameter values. Refer to the following Automatic Tune Mode table.
Table 7. Automatic Tune Mode Parameters Parameter Pre-tune Self-tune Automatic tune mode lock code Upper Display Adjustment Range On or OFF. Indication remains OFF if Pre-Tune cannot be used at this time. This applies if: a). The setpoint is ramping b). The process variable is less than 5% of span from the setpoint c). The primary or secondary output proportional bands = 0 On or OFF. Indication remains OFF if Self-Tune cannot be used at this time. This applies if either proportional band = 0.
Parameter Possible Values Option 2 module type No option fitted. Option 3 module type Auxiliary option A module type Auxiliary option B module type Upper/Main Display nonE Relay Lower Display OPn2 rLy Dual relay drLy SSR drive SSr Triac tri Linear voltage / current output Lin No option fitted.
7.4 Lock Code View In the event that a lock code is forgotten, the instrument lock code values can be seen in the lock code view. In this view the codes are read only, the codes can be changed from the mode to which they apply. Entry and Navigating in Lock Code View Mode Press shown. and together while the instrument is powering up until the CLoc display is Once in this mode Press to step between lock codes. Note: If there is no key activity for 2 minutes the instrument returns to Operator Mode.
SECTION 8: 1400+ CONTROLLER – MODEL GROUP These controllers combine technical functionality, field flexibility and ease of use to give you the best in comprehensive process control. Heat/Cool operation Loop alarm Auto/Manual Tuning Remote or Dual setpoint selection options Two process alarms RS485 Modbus and ASCII comms option Ramping setpoint PC configuration option 8.
Changing Parameter Values Press required. to navigate to the required parameter, then press or to set the value as Once the value is changed, the display will flash to indicate that confirmation of the change is required. The value will revert back if not confirmed within 10 seconds. Press to accept the change. Or Press to reject the change and to move onto the next parameter. Hold down and press to return to Select Mode.
Parameter Lower Display Upper Display Default Value When Visible When Visible N type: 0 to 1399 ºC Default Value JC NF N type: 32 to 2551 ºF for Europe rC R type: 0 to 1759 ºC rF R type: 32 to 3198 ºF SC S type: 0 to 1762 ºC SF S type: 32 to 3204 ºF tC T type: -240 to 400 ºC tF T type: -400 to 752 ºF t.C PTC T type: -128.8 to 400.0 ºC with decimal point T type: -199.9 to 752.
Parameter Lower Display Upper Display 2_10 Description ruL Scale Range Lower Limit +100 to Range Max Scale Range Lower Limit rLL Range Min. to Scale range Upper Limit 100 Decimal point position dPoS 1 2 3 Control Type CtYP Primary Output Control Action CtRL Alarm 1Type ALA1 Decimal point position in non-temperature ranges. 0 = XXXX 1 = XXX.X 2 = XX.XX 3 = X.XXX SnGL Primary control duAL Primary and Secondary control (e.g.
Parameter Process Low Alarm 2 value* Lower Display PLA2 Upper Display Description Default Value Range Min. to Range Max. Parameter repeated in Setup Mode Range Min. When Visible ALA2 = P_Lo ALA2 = dE ALA2 = b And Deviation Alarm 2 Value* dAL2 ±span from setpoint. Parameter repeated in Setup Mode 5 Band Alarm 2 value* bAL2 1 LSD to full span from setpoint.
Parameter Lower Display 1 Range Upper Display 0_10 Description 0 to 10 V DC output 2_10 2 to 10 V DC output 0_20 0 to 20 mA DC output 4_20 4 to 20 mA DC output Default Value When Visible Lin Retransmit Output 1 Scale maximum ro1H −1999 to 9999 Display value at which output will be maximum Range max Use1 = retS or retP Retransmit Output 1 Scale minimum ro1L −1999 to 9999 Range min Use1 = retS or retP Output 2 Usage USE2 Sec if dual control selected else A2_d Opn2 is not Display val
Parameter Bit rate Lower Display bAud Upper Display 1.2 1.2 kbps 2.4 2.4 kbps 4.8 4.8 kbps 9.6 9.6 kbps 19.2 19.2 kbps Communications Address Addr 1 Communications Write Enable CoEn r_ o Digital Input 1 Usage diGi Digital Input 2 Usage Remote Setpoint Input Range diG2 rinP Description Unique address assigned to the instrument in the range of 1 to 255 (Modbus), 1 to 99 (Ascii) Read only. Comms writes ignored r_ W Read / Write.
Parameter Remote Setpoint Offset Lower Display rSPo Upper Display CLoc 0 to 9999 Configura- Description Offset applied to RSP value. Constrained within Scale Range Upper Limit and Scale Range Lower Limit. Default Value 0 When Visible OpnA = rSPi 20 Always tion Mode Lock Code *Note: Alarm parameters marked * are repeated in Setup Mode. **Note: If diGi or diG2 = diS1 the remote setpoint input feature is disabled. The instrument uses the two internal setpoints (SP1 & SP2) instead.
Table 11. 1400+ Set Up Mode Parameters Parameter Input Filter Time constant Lower Display FiLt Upper Display Adjustment Range OFF, 0.5 to 100.0 secs in 0.5 sec increments Default Value When Visible 2.0 Always 0 Always Process Variable Offset OFFS ±Span of controller Primary Power PPW The current Primary Output Power. Read Only. N/A Always Secondary Power SPW The current Secondary Output power. Read Only. N/A Ctyp = duAL Primary Output Proportional Band Pb_P 0.
Parameter Output 2 Cycle Time Output 3 Cycle Time Lower Display CT2 CT3 Upper Display Adjustment Range 0.5, 1, 2, 4, 8, 16, 32, 64, 128, 256 or 512 secs. Not applicable to linear outputs 0.5, 1, 2, 4, 8, 16, 32, 64, 128, 256 or 512 secs. Not applicable to linear outputs Default Value 32 32 When Visible USE2 = Pri or Sec or bus USE3 = Pri or Sec or bus ALA1 = P_Hi Process High Alarm 1 value* PhA1 Range Min. to Range Max. Range Max. Process Low Alarm 1 value* PLA1 Range Min. to Range Max.
Parameter Setpoint Value Lower Display SP Local Setpoint Value LSP _LSP or *LSP Setpoint 1 Value SP1 _SP1 or *SP1 Setpoint2 Value SP2 _SP2 or *SP2 Set-up Lock Code SLoc Upper Display Adjustment Range Default Value When Visible Within scale range upper and lower limits Range minimum Always Within scale range upper and lower limits. _ or * before the legend indicates if this is the currently active SP Within scale range upper and lower limits.
8.3 1400+ Controllers - Operator Mode This is the mode used during normal operation of the instrument. It can be accessed from Select Mode, and is the usual mode entered at power-up. The available displays are dependent upon whether Dual or Remote Setpoint modes are being used, whether Setpoint Ramping is enabled and the setting of the Display Strategy parameter in Configuration Mode.
Table 12. 1400+ Operator Mode Displays Upper Display Lower Display When Visible PV Value Active SP Value Display strategy 1 and 2. (Initial Screen) Process Variable and target value of currently selected Setpoint. Local SP is adjustable in Strategy 2 PV Value Actual SP Value Display strategy 3 and 6 (Initial Screen) Process Variable and actual value of selected Setpoint (e.g. ramping SP value). Read only PV Value Blank Display strategy 4. (Initial Screen) Shows Process Variable.
Upper Display Lower Display Active Alarm Status ALSt When Visible Description mode. ramping. Adjustable except in Strategy 6 When any alarm is active. ALM indicator will also flash Upper display shows which alarm(s) are active. Inactive alarms are blank Alarm 1 Active 1 2 Alarm 2 Active L Loop Alarm Active Note: When an extended Operator Mode is configured the additional parameters are available after the above parameters.
8.5 Manual Control Mode To allow manual control to be selected in Operator Mode, poen must be enabled in Set Up Mode. Manual Mode can be selected using the front keys or by use of a digital input if one has been fitted and configured for this function. Selecting/deselecting Manual Control Mode Press the The key to toggle between Automatic and Manual control. indicator flashes continually in Manual Mode Press or to adjust the output power to the required value.
Parameter Alarm 1 Status Alarm 2 Status Setpoint Ramping Loop Alarm Status Loop Alarm Modbus Parameter No. 5 6 7 10 12 Notes RO RO R/W R/W R/W 1 = Active, 0 = Inactive 1 = Active, 0 = Inactive 1 = Enable(d), 0 = Disable(d) 1 = Active/Enable, 0 = Inactive/Disable Read to get loop alarm status. Write 0/1 to disable/enable. 13 Digital Input 2 RO State of Option B digital input. To set the bit value to 1 write FF, to set the bit value to 0 write 00.
Parameter Rate Modbus Parameter No. 9 Output 1 Cycle time 10 Scale Range Lower Limit 11 Scale Range Upper Limit 12 Alarm 1 Value 13 Alarm 2 Value Manual Reset 14 15 Overlap / Deadband 16 On / Off Differential 17 R/W R/W R/W R/W R/W R/W R/W R/W R/W Decimal Point Position 18 Output 2 Cycle Time.
Parameter Modbus Parameter No.
Parameter Controller commands Modbus Parameter No. ASCII Ident & Notes Message Types Z Type 3/4 50 R/W Only Type 3 / 4 ASCII messages are allowed with this parameter. The {DATA} field must be one of eight fivedigit numbers.
Parameter Modbus Parameter No. Controller Status Scan Table Equipment ID Serial Number Low Serial Number Mid Serial Number High Date of manufacture 122 123 124 125 126 ASCII Ident & Notes Message Types L Type 2 RO ] Type 2 RO RO RO RO RO RO Bit 0 Meaning Alarm 1 status. 0 = activated, 1 = safe Alarm 2 status. 1 0 = activated, 1 = safe Self-Tune status. 2 0 = disabled 1 = activated Change Indicator.
Parameter Modbus Parameter No. ASCII Ident & Notes Message Types Product Revision Level 129 RO Bits 0 – 7: Alpha part of PRL. (e.g. A = 01hex) Bits 8 – 15: Numeric part of PRL. (e.g.
SECTION 9: MANUALLY TUNING CONTROLLERS 9.1 Single Control Tuning (PID with Primary Output only) This simple technique balances the need to reach setpoint quickly, with the wish to limit setpoint overshoot at start-up or during process changes. It determines values for the Primary Proportional Band (Pb_P), Integral Time Constant (ArSt) and Derivative Time Constant (RAte) that allow the PID control algorithm to give acceptable results in most applications that use a single control device.
9.2 Dual Control Tuning (PID with Primary and Secondary Outputs) This simple tuning technique balances the need to reach setpoint quickly, with the wish to limit setpoint overshoot at start-up and during process changes. It determines values for the Primary Proportional Band (Pb_P), Secondary Proportional Band (Pb_S), Integral Time Constant (ArSt) and Derivative Time Constant (RAte) that allow the PID control algorithm to give acceptable results in most applications that use dual control (e.g. Heat & Cool).
6. Follow the instructions in the diagram below. At each stage, allow sufficient settling time before moving on to the next stage. Process Variable START Apply Power to the load. Does the Time Tb Yes PV continuously Oscillate? No Note the time Are the interval Ta Oscillations Yes decaying to zero? Set Pb_P = 0.8% Note the period of the decaying Set ArSt = Ta No oscillations (Tb) Multiply Pb_P setting by 1.5 Multiply Pb_P setting by 1.
9.4 Manually Fine Tuning A separate cycle time adjustment parameter is provided for each time proportioning control output. Note: Adjusting the cycle time affects the controllers operation; a shorter cycle time gives more accurate control but electromechanical components such as relays have a reduced life span. 1. Increase the width of the proportional band if the process overshoots or oscillates excessively. 2.
SECTION 10: MODBUS SERIAL COMMUNICATIONS All models support the Modbus RTU communication protocol. Some models also support an ASCII communication protocol. Where both Modbus and ASCII are supported, the protocol to be used is selected from Configuration Mode. The RS485 Communications Module must be fitted into Option Slot A in order to use serial communications. Refer to the relevant Model Group Section for the ASCII and Modbus Application Layer (parameter address/ident information).
10.2 Link Layer A Query (or command) is transmitted from the Modbus Master to the Modbus Slave. The slave instrument assembles the reply to the master. All of the instruments covered by this manual are slave devices, and cannot act as a Modbus Master. MODBUS SLAVE MASTER INSTRUMENT QUERY RESPONSE Modbus Link Layer A message for either a QUERY or RESPONSE is made up of an inter-message gap followed by a sequence of data characters. The inter-message gap is at least 3.5 data character times.
10.3 Device Addressing The instrument is assigned a unique device address by the user in the range 1 (default) to 255 using the Addr parameter in Configuration Mode. This address is used to recognise Modbus Queries intended for this instrument. The instrument does not respond to Modbus Queries that do not match the address that has been assigned to it. The instrument will also accept global Queries using device address 0 no matter what device address is assigned.
Read Coil/Input Status (Function 01 / 02) Reads the content of instruments output/input status bits at the specified bit address. Table 17. Read Coil/Input Status (Modbus Function 01/02) QUERY Address of 1st Bit Function 01 / 02 HI Function Number of Bits LO HI LO RESPONSE Number of Bytes First 8 bits 2nd 8 Bits 01 / 02 In the response the “Number of Bytes” indicates the number of data bytes read from the instrument. E.g. if 16 bits of data are returned then the count will be 2.
Force Single Coil (Function 05) Writes a single binary value to the Specified Instrument Bit address. Table 19. Force Single Coil (Modbus Function 05) QUERY Address of Bit Function 05 HI FF/00 RESPONSE Address of Bit Function 05 LO State to write HI LO 00 State written FF/00 00 The address specifies the address of the bit to be written to. The State to write is FF when the bit is to be SET and 00 if the bit is to be RESET. Note: The Response normally returns the same data as the Query.
Note: The Response normally returns the same data as the Query. Pre-Set Multiple Registers (Function 10 Hex) Writes a consecutive word (two-byte) value to the specified address range. Table 22.
Note: In the case of multiple exception codes for a single QUERY the Exception code returned is the one corresponding to the first parameter in error.
SECTION 11: ASCII COMMUNICATIONS This is simple ASCII protocol provides backwards compatibility with some older products. ASCII is not available in all models in the range. The Modbus protocol is recommended for future use. Refer to the relevant Model Group Section for the ASCII and Modbus Application Layer (parameter address/ident information). 11.
Table 24. ASCII Parameter Key {S} is the Start of Message character L (Hex 4C) or R (Hex 52). L is used for Controllers; R is used for Profilers. {N} is the slave device address (in the range 1 - 99); addresses 1 - 9 may be represented by a single digit (e.g. 7) or in two-digit form, the first digit being zero (e.g. 07). {P} {C} is a character which identifies the parameter to be interrogated/modified.
Type 2 Message L {N} {P} {C} * or R {N} {P} {C} * This type of message is used by the master device, to interrogate or modify a parameter in the addressed slave device.
Type 4 Message L {N} {P} I * or R {N} {P} I * This type of message is sent by the master device to the addressed slave device, following a successful Type 3 transaction with the same slave device. Provided that the {DATA} content and the parameter specified in the preceding Type 3 message are still valid, the slave device will then set the parameter to the desired value and will reply in the form: L {N} {P} {DATA} A * where {DATA} is the new value of the parameter.
SECTION 12: CALIBRATION MODE WARNING: CALIBRATION IS ONLY REQUIRED FOR INSTRUMENTS IN WHICH CALIBRATION ERRORS HAVE BEEN ENCOUNTERED. REFER TO CALIBRATION CHECK BELOW. CAUTION: Calibration must be performed by personnel who are technically competent and authorised to do so. Calibration is carried out during manufacture and is not normally required again during the lifetime of an instrument. 12.
12.3 Recalibration Procedure Recalibration is carried out in five phases as shown in the table below, each phase corresponds to an input range of the instrument. CAUTION: The 50mV phase MUST be calibrated before the thermocouple range. Table 26.
SECTION 13: APPENDIX 1 – GLOSSARY This Glossary explains the technical terms and parameters used in this manual. The entry type is also shown: General Definition: Terms normally applicable all models. Controller Definition: Terms applicable to Controller models only. VMD Controller Definition: Terms applicable to VMD Controller models only. Limit Controller Definition: Terms applicable to Limit Controller models only. Indicator Definition: Terms applicable to Indicator models only.
Alarm Hysteresis Type: General Parameter An adjustable band on the “safe” side of an alarm point, through which the process variable must pass before the alarm will change state, as shown in the diagram below. E.g. a high alarm’s hysteresis band is below the high alarm value, and a low alarm’s hysteresis is above the low alarm value. Also refer to Alarm Operation.
Alarm Operation Type: General Definition The different alarm types are shown below, together with the action of any outputs. Also refer to Alarm Hysteresis, Alarm Inhibit, Band Alarm, Deviation Alarm, Latching Relay, Logical Alarm Combinations, Loop Alarm, Process High Alarm and Process Low Alarm. Process High Alarm Direct-Acting Process High Alarm Reverse-Acting Process Low Alarm Direct-Acting Process Low Alarm Reverse-Acting Band Alarm Reverse-Acting Process Variable Output On. .Output Off Alarm Off. .
Alarm Inhibit Type: General Parameter Inhibits an alarm at power-up or when the controller Setpoint is switched, until that alarm goes inactive. The alarm operates normally from that point onwards. Also refer to Alarm Operation. Type: Controller Tuning Parameter Automatic Reset (Integral) Used to automatically bias the proportional output(s) to compensate for process load variations.
Bias (Manual Reset) Type: Controller Tuning Parameter Used to manually bias the proportional output(s) to compensate for process load variations. Bias is expressed as a percentage of output power and is adjustable in the range 0% to 100% (for Primary Output alone) or -100% to +100% (for both Primary and Secondary Outputs). This parameter is not applicable if the Primary output is set to ON/OFF control mode.
Communications Write Enable Type: General Definition Enables/disables the changing of parameter values via the RS485 communications link, if the communications option is installed. Possible settings are read only or read/write. Display code = CoEn, default setting = r_ W (read/write). Control Type Type: Controller Parameter Defines if a controller has one or two control outputs. Single outputs can drive the PV in one direction only (e.g. heat only, cool only, increase humidity etc).
below. If the process variable deviates from the setpoint by a margin greater than this value, alarm 1 becomes active. Display code = dAL1, Default value = 5. Also refer to Alarm Operation and Deviation Alarm 2 Value. Deviation Alarm 2 Value Type: General Parameter Applicable only if Alarm 2 is selected as a Deviation Alarm. It is similar to Deviation Alarm 1 Value. Display code = dAL2. Default value = 5. Also refer to Alarm Operation and Deviation Alarm 1 Value.
Input Span Type: General Definition The measuring limits, as defined by the Scale Range Lower and Scale Range Upper Limits. The trimmed span value is also used as the basis for calculations that relate to the span of the instrument (E.g. controller proportional bands) Also refer to Input Range, Scale Range Lower Limit and Scale Range Upper Limit. Integral Refer to Automatic Reset.
Logical Combination of Alarms Type: General Definition Two alarms may be combined logically to create an AND/OR situation. Any suitable output may be assigned as a Logical Alarm Output, configured for Reverse-acting or Direct action. Also refer to Alarm Operation Table 27.
Loop Alarm Time Type: Controller Parameter When On-Off control is selected and loop alarm is enabled, this parameter determines the duration of the limit condition after which the loop alarm will be activated. It may be adjusted within the range of 1 second to 99 minutes 59 seconds. This parameter is omitted from the Set-up mode display sequence if On-Off control is not selected or loop alarm is disabled. Display code = LAti, Default setting is 99:59. Also refer to Loop Alarm Enable.
Also refer to Cascade Control, Retransmit Output, Remote Setpoint, Serial Communications, Setpoint Modulating Valve Type: VMD Controller Definition A valve that can be positioned anywhere between fully closed and fully open by means of an incorporated motor. A typical application would be controlling temperature in a furnace heated by gas burners. Some modulating valve motors require linear (mA or VDC) signals to position the valve. These require standard Process Controllers (using PI control).
Overlap/Deadband Type: Controller Parameter Defines the portion of the primary and secondary proportional bands (Pb_P + Pb_S) over which both outputs are active (Overlap), or neither is active (Deadband). It is adjustable in the range -20% to +20% of the two proportional bands added together. Positive values = Overlap, negative values = Deadband. This parameter is not applicable if the primary output is set for On-Off control or there is no Secondary Output.
PI Control Type: Controller Definition Proportional and Integral (PI) Control is used to control Modulating Valves. It is similar to PID Control, but without Derivative (Rate) action that causes excessive valve movement. Also refer to Modulating Valve, PID Control, Rate, Tuning and Valve Motor Drive Control. PID Control Type: Controller Definition Proportional Integral and Derivative control maintains accurate and stable levels in a process (e.g. temperature control).
Pre-Tune Type: Controller Definition The Pre-Tune facility artificially disturbs the start-up pattern so that a first approximation of the PID values can be made prior to the setpoint being reached. During Pre-Tune, the controller outputs full Primary Power until the process value has moved approximately halfway to the setpoint. At that point, power is removed (or outputs full Secondary Power for Dual Control), thereby introducing an oscillation.
Primary Proportional Band Type: Controller Tuning Parameter The portion of the input span over which the Primary Output power level is proportional to the process variable value. It may be adjusted in the range 0.0% (ON/OFF) to 999.9%. Applicable if Control Type is Single or Dual. For dual control a Secondary Proportional band is used for the second output. The Control Action can be Direct or Reverse acting. The Display value = Pb_P, default value = 5.0%.
Rate (Derivative) Type: Controller Tuning Parameter Rate is adjustable in the range 0 seconds (OFF) to 99 minutes 59 seconds. It defines how the control action responds to the rate of change in the process variable. This parameter should not be used in modulating value applications as it can cause premature wear due to constant small adjustments to the valve position. The Rate parameter is not available if primary control output is set to On-Off.
Display value = rSPo, default value = 0. Also refer to Remote Setpoint, Scale Range Upper Limit and Scale Range Lower Limit. Retransmit Output Type: General Definition A linear DC voltage or mA output signal, proportional to the Process Variable or Setpoint, for use by slave controllers or external devices, such as a Data Recorder or PLC. The output can be scaled to transmit any portion of the input or setpoint span. Also refer to Input Span, Master & Slave, Process Variable and Setpoint.
Also refer to Process Variable, Retransmit Output, Retransmit Output 3 Scale Minimum, Scale Range Upper Limit and Setpoint. Retransmit Output 3 Scale Minimum Type: General Parameter Defines the value of the process variable, or setpoint, at which Retransmit Output 3 will be at its minimum value. It is similar to Retransmit Output 1 Scale Minimum. Display code = ro3L, default value = Scale Range Lower Limit.
Self-Tune Type: Controller Tuning Definition Self-Tune continuously optimises tuning while a controller is operating. It uses a pattern recognition algorithm, which monitors the process error (deviation). The diagram shows a typical application involving a process start up, setpoint change and load disturbance. Temperature Setpoint 2 Load Disturbance Setpoint 1 Setpoint Change Time Figure 39. Self-Tune Operation The deviation signal is shown shaded and overshoots have been exaggerated for clarity.
Set Valve Opened Position Type: VMD Controller Parameter When Valve Position Indication is to be used on Valve Motor Controllers, this parameter defines the input value that will be measured by the Auxiliary Input, when the valve is fully opened. The valve must driven to its “Open” end stop before setting this parameter. It must not be used to limit valve movement, separate Valve Close and Open Limit parameters are available for this purpose.
setpoint at power up, or when switching back to automatic mode from manual control, will be equal to the current process variable value. The actual setpoint will rise/fall at the ramp rate set, until it reaches the target setpoint value. Setpoint ramping is used to protect the process from sudden changes in the setpoint, which would result in a rapid rise in the process variable. Display code = rP, default setting = OFF (blank). Also refer to Manual Mode, Setpoint, Setpoint Ramp Enable and Setpoint Select.
Display code = tArE, default setting = diSA (disabled). Also refer to Indicator, Process Variable, and Offset. Three Point Stepping Control Refer to Valve Motor Control. Type: VMD Controller Definition Time Proportioning Control Type: Controller Definition Time proportioning control is accomplished by cycling the output on and off, during the prescribed cycle time, whenever the process variable is within the proportional band. The control algorithm determines the ratio of time (on vs.
Valve Motor Drive Control Type: VMD Controller Definition Valve Motor Drive Controllers are designed to control Modulating Valves using a special “Open Loop” Valve Motor Drive (VMD) PI control algorithm. Output signals are provided to move the valve further open, or further closed when the process is higher or lower than the desired setpoint. When on setpoint, no output is required to maintain control unless load conditions change. This known as Three-Point Stepping control.
SECTION 14: APPENDIX 2 – SPECIFICATION 14.1 Universal Input General Input Specifications Input Sample Rate: Digital Input Filter time constant Input Resolution: Input Impedance: Isolation: PV Offset: PV Display: Four samples/second. 0.0 (OFF), 0.5 to 100.0 seconds in 0.5 second increments. 14 bits approximately. Always four times better than display resolution. 10V DC: 47KΩ 20mA DC: 5Ω Other ranges: Greater than 10MΩ resistive Isolated from all outputs (except SSR driver).
Note: Defaults to °F for USA units. Defaults to °C for no n-USA units. The Configuration Mode parameters, Scale Range Upper Limit and Scale Range Lower Limit, can be used to restrict range. Thermocouple Performance Calibration: Measurement Accuracy: Linearisation Accuracy: Cold Junction Compensation: Temperature Stability: Supply Voltage Influence: Relative Humidity Influence: Sensor Resistance Influence: Sensor Break Protection: Complies with BS4937, NBS125 and IEC584. ±0.1% of full range span ±1LSD.
RTD Performance Type: Calibration: Measurement Accuracy: Linearisation Accuracy: Temperature Stability: Supply Voltage Influence: Relative Humidity Influence: Sensor Resistance Influence: Lead Compensation: RTD Sensor Current: Sensor Break Protection: Three-wire Pt100. Complies with BS1904 and DIN43760 (0.00385Ω/Ω/°C). ±0.1% of span ±1LSD. Better than ±0.2°C any point, any 0.1°C range ( ±0.05°C typical). Better than ±0.5°C any point, any 1 °C range. 0.01% of span/°C change in ambient temperature.
14.2 Auxiliary Inputs Input Sampling rate: Input Resolution: Input types: 4 per second Measurement Accuracy (reference conditions): Input resistance: ±0.25% of input span ±1 LSD 13 bits minimum 4 to 20mA, 0 to 20mA, 0 to 10V, 2 to 10V, 0 to 5V, 1 to 5V. The Full Auxiliary input in Option Slot B also supports 0 to 100mv and Potentiometer (2KΩ or higher).
Specifications of Output Types Single Relay: Contact Type: Control Rating: Single pole double throw (SPDT). 2A resistive at 240V AC (120V when directly driving motorised valves). Limit Controller has a fixed 5A latching relay, in Option Slot 1. 2A resistive at 240V AC >500,000 operations at rated voltage/current. >100,000 operations at rated voltage/current. Basic Isolation from universal input and SSR outputs. 2 x Single pole single throw (SPST) with shared common.
Triac: Operating Voltage Range: Current Rating: Max. Non-repetitive Surge Current (16.6ms): Min. OFF-State dv/dt @ Rated Voltage: Max. OFF-State leakage @ Rated Voltage: Max. ON-State Voltage Drop @ Rated Current: Repetitive Peak OFF-state Voltage, Vdrm: Isolation: Linear DC: Resolution: Update Rate: Ranges: Load Impedance: Accuracy: When used as control output: Isolation: Use as 0 to 10VDC transmitter power supply* Indicators only.
14.5 Control Specifications Automatic Tuning Types: Proportional Bands: Automatic Reset (Integral Time Constant): Rate (Derivative Time Constant): Manual Reset (Bias): Deadband/Overlap: ON/OFF Differential: Motor Travel Time Minimum Motor On Time Auto/Manual Control: Cycle Times: Setpoint Range: Setpoint Maximum: Setpoint Minimum: Setpoint Ramp: Pre-Tune, Self-Tune. 0 (ON/OFF control), 0.5% to 999.9% of input span at 0.1% increments. ON/OFF control not valid for VMD controllers. 1s to 99min 59s and OFF.
14.8 Reference Conditions Ambient Temperature: Relative Humidity: Supply Voltage: Source Resistance: Lead Resistance: 20°C ±2°C. 60 to 70%. 100 to 240V AC 50Hz ±1%. <10Ω for thermocouple input. <0.1Ω/lead balanced (Pt100). 14.9 Operating Conditions Ambient Temperature (operating): Ambient Temperature (storage): Relative Humidity: Altitude: Supply Voltage: Power Consumption: Source Resistance: PT100 Input Lead Resistance: 0°C to 55°C. -20°C to 80°C. 20% to 95% non-condensing. Up to 2000m above sea level.
SECTION 15: APPENDIX 3 – PRODUCT CODING Model Code P1400 - x - x - x - x - x - x - x - x - x - x - Sxxx Option Slot 1 Not fitted 0 Relay Output 1 DC Drive Output for SSR 2 Linear DC Output 3 Triac Output 8 Option Slot 2 Not fitted Relay Output 0 0 1 DC Drive Output for SSR 2 Linear DC Output 3 Triac Output 8 Option Slot 3 Not fitted Relay Output 0 0 1 DC Drive Output for SSR 2 Linear 0-10V DC Output 3 Transmitter PSU 4 Option Slot A** and Display Color Not fitted Red Upper/Red L
Manual Language No Manual 0 English 1 French 2 German 3 Italian 4 Spanish 5 Mandarin 6 9 English/French/German/Italian/Spanish - Concise Manuals only ** Slot A Basic Aux must not be installed if Slot B Full Aux is fitted. *** Slot B is only available on 1/4 DIN controllers.