Quick Start Manual
14
Running The Profile
Press the PROF key until 1 is displayed in the Program Display. Press the Run/HOLd key until
1 is displayed in the Segment Display and Final SP is displayed in the message display. Make
changes with the UP and Down arrow keys. Press the SCROLL key to move to the next
display.
Segment Description Message Display Setting In Lower Display
Setpoint Final SP 250
#1 Ramp Time Time 0.10
Event Status Event 0001
Setpoint Final SP 250 (or “- - - -“)
#2 Soak Time Time 1.00
Event Status Event 0001
Setpoint Final SP 70
#3 Ramp Time Time 0.25
Event Status Event 0000
Setpoint Final SP 70 (or “- - - -“)
#4 Time Time
End *
Event Status Event 0000
* Press and hold the Down arrow key until “End” is displayed.
Press the mode key to return to the base mode. Press the PROF key until 1 is displayed in the
segment display. Press the Run/HOLd key to start the profile.