Quick Start Manual

8
STEP DESCRIPTION MESSAGE
DISPLAY
FUNCTION AVAILABLE SETTING
5 Program Lock LockProg Defines whether the
operator is permitted to
change program
definitions while a
program is running/held
On - No changes permitted
Off - changes permitted
6 Power Fail
Recovery
Period
Recovery Defines length of power
loss before automatic
return to Base Mode
after restoration of
power, regardless of
Recovery Type.
1:00 - 24:59
NOTE: If the real time clock
option has not been provided,
changing this value to 0.01 will
allow selection of Recovery Type.
Setting this to 00:00 will force a
return to Base Mode.
7 Power Fail
Recovery Type
Rec Type Defines response to
restoration of power
after a power loss. This
parameter does not
appear if Recovery is
set to 0.00. These
settings can be
overridden by the
Recovery parameter.
cont - Continue with mode of
operation at time of power failure.
rESt - Restart program running at
time of power failure. If one was
not running, return to Base Mode.
PFH - Setpoint and event outputs
are held at values at time of
power loss. P.F. Hold is
displayed until a key other than
RUN/HOLD is pressed. Pressing
the RUN/HOLD key will continue
the profile if one was running.
Holding this key for more than
five seconds will abort the profile.
8 Time of day
RTC Time **
Sets clock time of real-
time clock option
1:00 - 24:59
9 Day of week
RTC Day **
Sets day of real-time
clock option
Sun through SAt
10 External
Selection
Ext. Sel ***
Defines functions which
may be controlled
externally
nonE = No external selection
SEL = Program selection only
run = Only Run, Hold, Abort and
x60 functions
both = All program selection and
run control functions
* The Final Setpoint value for the End Segment of each program.
** Only if real-time clock is fitted.
*** Only if external options are fitted.