User guide
93
Digital (Remote Program Control) Inputs, Outputs
Type: Voltage-free contact compatible
Number Available: Six: Run/Hold, Time Base x60, Abort Three (binary-coded) Program
Select.
Active State: Max. Contact Resistance (closed) = 50 ohms
Non-Active State: Min. Contact Resistance (open) = 5,000 ohms
Max. Voltage for "1” = 24.0V
Max. Input Delay
(OFF-ON): 0.25 seconds
Min. Input Delay
(ON-OFF): 0.25 seconds