User guide
92
Program Specifications
Programs: Eight, each with free-form segments
Length of Programs: Adjustable in the range 1 to 16 segments; programs
cascadable - maximum length 121 segments.
Segment Types: Ramp, Dwell, Join, Repeat, or End.
Program Cycling: Range 1 to 9999, infinite.
Delayed Start: May be set in the range 0 to 99:59 (hours:minutes).
One setting applies to all programs.
Control: Run, Hold, Abort, Time Base x60 (local or remote);
Select Program (local or remote); Jump to next Segment.
Start From: Either current process variable value or controller setpoint value.
Go To: Base Mode or Off Mode
End On: Final Value or controller setpoint.
Deviation/Hold: Off, below setpoint only, above setpoint only or above and below
setpoint. On ramps only, on dwells only, or on both ramps and
dwells. Auto/Hold band may be set from 0 to input span.
Time Base: Either hours:minutes or minutes:secs (x60) preprogrammable or
may be set during Program Run.
Segment Time: May be set in the range 0 to 99:59 (hours:minutes or
minutes:seconds).
Ramp Rate: 0 to 9999 least significant digits per hour or minute.
End of Program Output
Type: Relay
Contact Type: SPDT
Rating: 5A resistive @ 120/240V AC
Lifetime: >100,000 operations @ rated voltage/current
Isolation: Inherent
Event Outputs - Option
Type: Relay (4)
Contact Type: SPST
Rating: 5A resistive @ 120/240V AC
Lifetime: >100,000 operations @ rated voltage/current.
Isolation: Inherent
Programmability: Each event is programmable to either OFF or ON for each segment.