User guide

91
Control Specifications
Control Types: PID, PID/ON-OFF2, ON-OFF
Automatic Tuning Types: Pre-Tune and Auto-Tune
Proportional Bands: 0 (OFF) 0.5% - 999.9% of input span @ 0. 1 % increments
Auto Reset: 1 s-99min 59sec/repeat and OFF
Rate: 0 (OFF) - 99min 59sec
Manual Reset (Bias): Adjustable in the range 0-100% of output power (single output) or -
100% to +100% of output power (dual output)
Deadband/Overlap: -20% to +20% of proportional band 1 + proportional band 2
ON/OFF Hysteresis: 0. 1 % to 10.0% of input span
Auto/Manual Control: User-selectable with "bumpless" transfer into and out of Manual
control.
Cycle Times: Selectable from 0.5sec to 512sec in binary steps
Setpoint Range: Limited by Setpoint Maximum and Setpoint Minimum.
Setpoint Maximum: Limited by Setpoint and Range Maximum.
Setpoint Minimum: Limited by Range Minimum and Setpoint.
Alarms
Maximum Number: Two "soft" alarms plus Loop Alarm
Maximum # Outputs: Up to 2 outputs can be used for alarm purposes
Combination Alarms: Logical OR or AND of alarms to an individual
hardware output is available.
Hysteresis: 1 LSD to 1 0% of span.
Loop Alarm: Detects faults in the control feedback loop by continuously
monitoring process variable response to the control output(s).