MIC 1422 MICROBASED CONTROLLER INSTRUCTION MANUAL i E-90 PN 136108 REVISION 10-07
ii
TABLE OF CONTENTS TABLE OF CONTENTS .................................................................................................. iii SECTION 1: PRODUCT DESCRIPTION ....................................................................... 1 1.1 General .................................................................................................................. 1 1.2 Displays................................................................................................................. 2 1.
SECTION 7: TEST MODE ........................................................................................... 43 7.1 Test Mode Description ........................................................................................ 43 SECTION 8: CONFIGURATION MODE ...................................................................... 45 8.1 Configuration Mode Description .......................................................................... 45 8.2 Hardware Definition Code ................................
SECTION 1: PRODUCT DESCRIPTION 1.1 General This instrument is a microprocessor based single loop controller capable of measuring, displaying and controlling temperature, pressure, flow, and level from a variety of inputs. Most outputs are easily tuned using the instrument Pre-Tune and Auto-Tune, or RaPID (Response assisted PID) functions. Control functions, alarm settings and other parameters are easily entered through the front keypad.
1.2 Displays Each instrument is provided with dual displays and status indicators as shown in Figure 1 -1. The upper display (RED) displays the value of the process variable. The lower display (GREEN) displays the setpoint value. 1.3 Control The instrument can be programmed for on-off, time proportioning, or current proportioning control implementations depending on the model number. A second control output is an available option.
FIGURE 1-1 Keys and Indicators 1.5 Process Variable/Setpoint Value Re-Transmission Output If the instrument is specified with this option, this output may be scaled over any desired range and re-transmitted.
4
SECTION 2: INSTALLATION AND WIRING 2.1 Mounting Electrical code requirements and safety standards should be observed and installation performed by qualified personnel. The electronic components of the instrument may be removed from the housing during installation. To remove the components, grip the side edges of the front panel and pull the instrument forward. During re-installation, the vertically mounted circuit boards should be properly aligned in the housing.
FIGURE 2-2 Main Dimensions MIC1422 FIGURE 2-3 Panel Mounting the Controller 6
2.2 Wiring Guidelines Electrical noise is a phenomenon typical of industrial environments. The following are guidelines that must be followed to minimize the effect of noise upon any instrumentation. Installation Considerations Listed below are some of the common sources of electrical noise in the industrial environment: • • • • Ignition Transformers Arc Welders Mechanical contact relay(s) Solenoids Before using any instrument near the device listed, the instructions below should be followed: 1.
AC Power Wiring Neutral (For 115 VAC) It is good practice to assure that the AC neutral is at or near ground potential. To verify this, a voltmeter check between neutral and ground should be done. On the AC range, the reading should not be more than 50 millivolts. If it is greater than this amount, the secondary of this AC transformer supplying the instrument should be checked by an electrician. A proper neutral will help ensure maximum performance from the instrument.
Noise Suppression At The Source Usually when good wiring practices are followed no further noise protection is necessary. Sometimes in severe electrical environments, the amount of noise is so great that it has to be suppressed at the source. Many manufacturers of relays, contactors, etc. supply "surge suppressors" which mount on the noise source. For those devices that do not have surge suppressors supplied, RC (resistancecapacitance) networks and/or MOV (metal oxide varistors) may be added.
FIGURE 2-5 2.3 Sensor Placement (Thermocouple or RTD) Two-wire RTDs should be used only with lead lengths less than 10 feet. If the temperature probe is to be subjected to corrosive or abrasive conditions, it should be protected by the appropriate thermowell.
FIGURE 2-6 Wiring Label 1/4 DIN 11
2.4 Input Connections In general, all wiring connections are made to the instrument after it is installed. Avoid Electrical Shock. AC power wiring must not be connected to the source distribution panel until all wiring connection procedures are completed. Caution: This equipment is designed for installation in an enclosure which provide adequate protection against electric shock. Local regulations regarding electrical installation should be rigidly observed.
FIGURE 2-7A 24V Nominal AC/DC Supply The supply connection for the 24V AC/DC option of the instrument are as shown below. Power should be connected via a two pole isolating switch and a 315 mA slow-blow (anti-surge type T) fuse. With the 24V AC/DC supply option fitted, these terminals will accept the following supply voltage ranges: 24V (nominal) AC 50/60 Hz 24V (nominal) DC - 20 - 50 V 22 - 65 V FIGURE 2-8 Thermocouple (T/C) Input Make thermocouple connections as illustrated below.
FIGURE 2-9 RTD Input Make RTD connections as illustrated below. For a three wire RTD, connect the resistive leg of RTD to terminal 1 and the common legs to terminals 2 and 3. For a two wire RTD, connect one leg to terminal 2 and the other leg to terminal 3 as shown below. A jumper wire supplied by the customer must be installed between terminals 2 and 3. Input conditioning jumper must be positioned correctly (see Appendix B) and Hardware Definition Code must be correct (see Section 8, Configuration Mode).
FIGURE 2-11 Remote Digital Communications - RS485 Make digital communication connections as illustrated below. FIGURE 2-12 Remote Setpoint Input - V/mA/mV and Potentiometer Connections are illustrated below. Terminal 6 is positive and terminal 7 is negative. The remote setpoint input can be configured for linear DC mv, linear DC mA, linear DC Volt or potentiometer.
FIGURE 2-13 Remote Setpoint Selection Connections are made as shown. FIGURE2-14 Dual Setpoint Selection Connections are made as shown.
2.5 Output Connections FIGURE 2-15 Relay Output 1 (Control Output 1) Connections are made to Output 1 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC. FIGURE 2-16 SSR Driver Output 1 (Control Output 1) Connections are made to Output 1 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms. FIGURE 2-17 mADC Output 1 (Control Output 1) Make connections for DC Output 1 as illustrated below.
FIGURE 2-18 Relay Output 2 (Control Output 2 OR Alarm 2) Connections are made to Output 2 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC. FIGURE 2-19 SSR Driver Output 2 (Control Output 2 OR Alarm 2) Connections are made to Output 2 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms. FIGURE 2-20 mADC Output 2 (Control Output 2) Make connections for DC Output 2 as illustrated below.
FIGURE 2-21 Relay Output 3 (Alarm 1) Connections are made to Output 3 relay as illustrated below. The contacts are rated at 2 amp resistive, 120/240 VAC. FIGURE 2-22 SSR Driver Output 3 (Alarm 1) Connections are made to Output 3 SSR Driver as illustrated below. The solid state relay driver is a non-isolated 0-4 VDC nominal signal. Output impedance is 250 ohms. FIGURE 2-23 mADC Output 3 (Recorder Output Only) Make connections for DC output 3 as illustrated below.
20
SECTION 3: OPERATION 3.1 Control Capability The capabilities available in a specific unit are dependent upon the hardware options specified when the instrument is ordered. Refer to Appendix E for the decoding of the instrument model number. Current proportioning control cannot be implemented if a current output was not ordered.
3.3 Direct/Reverse Operation of Outputs Direct operation is typically used with cooling applications. On-Off direct output(s) will turn on when the process variable exceeds setpoint. Proportional direct output(s) will increase the percentage of output as the process value increases within the proportional band. Reverse operation is typically used with heating applications. On-Off reverse output(s) will turn off when the process variable exceeds setpoint.
When the unit is operating in the Control Mode, the control algorithm determines the output % required to correct for any difference between the process value and the setpoint. The output calculation is affected by Tune Mode parameter adjustments. See Figure 3-1 for proportional bandwidth effect on the output. 3.6 Current Proportioning Control Current Proportioning control can be implemented on units provided with mADC current output(s).
FIGURE 3-1 Proportional Band 1 24
3.7 Power Up Procedure Verify all electrical connections have been properly made before applying power to the instrument. If the instrument is being powered for the first time, it may be desirable to disconnect the controller output connections. The instrument will be into control following the power up sequence and the output(s) may turn ON. During power up, a self-test procedure is initiated during which all LED segments in the two front panel displays appear and all LED indicators are ON.
UP KEY • • Increase the displayed parameter value. Increase setpoint. DOWN KEY • • Decrease the displayed parameter value. Decrease setpoint. • plus to view the current Hardware Definition Code setting. 3.9 Front Panel Indicators OP1 Indicates the state of the Output 1 relay or SSR driver. When the indicator is ON the relay is energized or the SSR driver is ON. OP2 Indicates the state of the Output 2 relay or SSR driver. When the indicator is ON the relay is energized or the SSR driver is ON.
SECTION 4: CONTROL MODE 4.1 Operation After the instrument has performed its power up self test, the Control Mode is active with the setpoint in the lower display and the process variable in the upper display. To view the various parameters in the Control Mode, press the SCROLL key. The lower display shows the parameter name and the upper display shows the current setting of the parameter. To change the setpoints, use the UP and DOWN keys.
4.3 Override Feature While the instrument is being used with either Dual Setpoint operation or Remote Setpoint operation, the Override feature is available. This enables the active setpoint selected by the digital input to be manually overridden from the keypad. To engage the Override feature, with the instrument displaying the desired setpoint, press the UP and DOWN keys simultaneously. This will cause the left-most character of the lower display to show a flashing " ".
If a break is detected in the sensor circuit, the upper display will show: 4.6 Manual Control (Percent Output) Manual Control is not applicable if the Auto/Manual selection in Enable Mode is disabled. If enabled, the Manual Mode may be entered by pressing the AUTO/MANUAL key. The Manual Mode status LED will begin to flash indicating that the Manual Mode is in use. Shifting from the Control to the Manual Mode is bumpless.
4.7 Setup Modes The Setup Modes contain parameters which configure the instrument and affect how the control functions. To access the Setup Modes from the Control Mode, press the SCROLL key until the lower display reads Mod. Press the DOWN key, then press the SCROLL key to view the different modes available. The following sections contain instructions for accessing and using the various Setup Modes. To return to Control Mode, press the SCROLL key until CtrL is displayed, then press the DOWN key.
SECTION 5: TUNE MODE 5.1 Tune Mode Description The Tune Mode contains parameters concerning tuning of the instrument. To access the Tune Mode from the Control Mode, press the SCROLL key until Mod is displayed. Press the DOWN key. This puts the control in Setup Mode. Press the SCROLL key until tunE is displayed. Press the DOWN key to access the Tune Mode. A series of parameters is available by pressing the SCROLL key. The parameter tag name will appear the lower display with the upper display blank.
5.2 Manual Tuning Method 1. Cycle Time - Time Proportioning Outputs A. Adjusting the cycle time affects instrument operation 1. Shorter Cycle Time a. More accurate control b. Shorter life span of electromechanical components 2. Proportional Bandwidth A. Proportional Bandwidth is the inverse of gain. Increased Bandwidth = Decreased Gain B. Increase the Proportional Bandwidth if: 1. The process overshoots excessively 2. The process oscillates excessively C. Decrease the Proportional Bandwidth if: 1.
Table 5-1 Tune Mode Parameters STEP DESCRIPTION 1 Local Setpoint 2 11 Remote Setpoint Setpoint 1 Value Setpoint 2 Value Input Correct Output 1 % Output 2% 1st Output Prop. Band 2nd Output Prop.
FIGURE 5-1 Proportional Band & Deadband/Overlap 34
SECTION 6: ALARM MODE 6.1 Alarm Mode Description The Alarm Mode contains parameters concerning process alarms. To access the Alarm Mode from the Control Mode, press the SCROLL key until Mod is displayed. Press the DOWN key. This puts the control in Setup Mode. Press the SCROLL key until ALA is displayed. Press the DOWN key to access the Alarm Mode. A series of parameters is available by pressing the SCROLL key. The parameter tag name will appear in the lower display with the upper display blank.
Table 6-1 Alarm Mode Parameters STEP 1 DESCRIPTION Alarm 1 Type DISPLAY CODE ALA1 2 3 Alarm 2 Type Alarm Inhibit ALA2 Inhi 4a Process High Alarm 1 Process Low Alarm 1 Band Alarm 1 Deviation Alarm 1 Alarm Hysteresis Process High Alarm 2 Process Low Alarm 2 Band Alarm 2 Deviation Alarm 2 Alarm 2 Hysteresis Loop Alarm Enable Loop Alarm Time PHA1 4b 4c 4d 5 6a 6b 6c 6d 7 8 9 1 2 2 AVAILABLE SETTINGS P-hi=Proc High nonE=No Alarm bAnd=Band dE=Deviation P-Lo=Proc Low Same selection as ALA1 nonE=No Inh
FIGURE 6-1 Alarm Actuation 37
38
FIGURE 6-2 Alarm Hysteresis 39
6.2 Loop Alarm Enable This parameter is the means by which the user can enable or disable the Loop Alarm. The Loop Alarm is a special alarm which detects faults in the control feedback loop by continuously monitoring process variable response to the control output(s). The Loop Alarm, when enabled, repeatedly checks the control output(s) for being at the maximum or minimum limit.
6.4 Logical Combination of Alarms Two alarms may be combined logically to create an AND/OR situation. They may be configured for Reverse-acting or Direct-acting. Either Output 2 or Output 3 may be assigned as Logical Outputs.
FIGURE 6-3 Asymmetrical Band Alarm 42
SECTION 7: TEST MODE 7.1 Test Mode Description The Test Mode allows manual control of the instrument outputs in order to test their operation. To access the Test Mode from the Control Mode, press the SCROLL key until Mod is displayed. Press the DOWN key. This puts the control in Setup Mode. Press the SCROLL key until tESt is displayed. Press the DOWN key to access the Test Mode. A series of parameters is available by pressing the SCROLL key.
44
SECTION 8: CONFIGURATION MODE 8.1 Configuration Mode Description The Configuration Mode contains parameters concerning output functions of the instrument. To access the Configuration Mode from the Control Mode, press the SCROLL key until Mod is displayed. Press the DOWN key. This puts the control in Setup Mode. Press the SCROLL key until ConF is displayed. Press the DOWN key to access the Configuration Mode. A series of parameters is available by pressing the SCROLL key.
STEP DESCRIPTION 5 Output 2 Usage DISPLAY CODE USE2 6 Output 3 Usage USE3 7 8 9 10 Com Bit Rate Com Parity Com Address CJC Enable CbS CPAr CAd CJC 11 12 Decimal Position Engineering Units Upper Engineering Units Lower Setpoint Upper Limit Setpoint Lower Limit Remote Setpoint Maximum Remote Setpoint Minimum Output 1% Limit Process Output Upper Process Output Lower dPoS Euu Out2=Control (opposite of Out1 action) Hy_r=Alm Hyst Rev Act** Hy_d=Alm Hyst Dir Act*** LP-r=Loop Reverse LP-d=Loop Direct
* The Hardware Definition Code and input jumper configuration may need to be changed. See Appendices A and B. ** If Remote Setpoint Input has been selected in the Hardware Definition Code, this parameter will appear in the normal Program Mode parameter sequence. The upper display shows a product code which defines the input range. The factory setting depends on code selected, see Appendix B.
8.2 Hardware Definition Code The Hardware Definition Code is used to represent the hardware installed (input type, Output 1 type, Output 2 type and Output 3 type); this must be compatible with the hardware actually installed. It can be accessed, with the instrument in Configuration Mode (with a prompt inPS, etc. displayed), by simultaneously depressing the DOWN and SCROLL keys.
The displayed code may be incremented/decremented using the UP/ DOWN keys as required. The maximum setting available is 4777. For example, the code for a thermocouple input, DC 4-20 mA Output 1 and relay Output 3 would be 2701. When the code is first altered, the code display will flash, until the desired value is displayed and confirmed by pressing the Auto/Manual key.
NOTE: It is essential that this code is changed whenever there is a change to the instrument's hardware configuration (change of input/output type, alarm/ retransmit output added/removed etc.). The instrument's software depends upon this code to ensure that the instrument operates correctly. To exit from the Hardware Definition Code display, depress the DOWN and SCROLL keys simultaneously.
SECTION 9: CALIBRATION MODE 9.1 Entering Calibration Mode To enter the Calibration Mode from Setup Mode: 1. Press the SCROLL key until CAL appears in the message display 2. Press the DOWN key to enter the Calibration Mode. NOTE: Calibration should be attempted only on Controllers on which calibration errors have been encountered (see CALIBRATION CHECK). 9.2 Calibrating The Universal Input Equipment Required 1. Input source with an accuracy better than +/- 0.05 of reading: a.
3. Enter Calibration Mode (Section 9.1). The upper display will then show Input Type Number, in the form: iP_I and the lower display will show: CAL Using the UP/DOWN keys, change the input type number as required (see Table 9-1). NOTE: If required, only one input type may be calibrated. Exception: If it is required to calibrate the thermocouple input (Input Type 5), it is necessary first to calibrate the DC 0 - 50 mV input (Input Type 1). Table 9-1 Universal Input Type Selection Input Type No.
9.3 Calibrating The Secondary Analog Input Equipment Required 1. DC linear input source (0 - 5 V and 0 - 20 mA) with an accuracy better than +/0.05% of reading. 2. Case assembly, wired for appropriate input supply (90 - 264V AC 50/60 Hz, 20 50 VAC 50/60 HZ or 22-65 VDC). Calibration Procedure 1. Ensure that the Controller is powered off and that the line power lead is disconnected. On the CPU PCB, configure link jumpers LJ10 and LJ11 (see Figure A-2).
6. To calibrate all inputs, repeat Steps 1 to 4 for each of the other input types (see Table 9-2) until all three secondary analog input types have been successfully calibrated. Table 9-2 Secondary Analog Input Type Selection Input Type No.
SECTION 10: ENABLE MODE 10.1 Enable Mode Description The Enable Mode controls access to the various modes available. To access the Enable Mode from the Control Mode, press the SCROLL key until Mod is displayed. Press the DOWN key. This puts the control in Setup Mode. Press the SCROLL key until EnAb is displayed. Press and hold the DOWN key for five seconds. The lower display will read PASS. Use the UP and DOWN keys to change the upper display to the correct Pass Code. Press the SCROLL key.
Table 10-1 Enable Mode Parameters STEP DESCRIPTION 1 Enable Setpoint Change DISPLAY CODE ESP 2 *Enable Pre Tune EPre 3 Enable Auto Tune EAut 4 Enable RaPID Tune ErAP 5 Enable Power-Up PreTune EPtn 6 Enable Tune Mode Etun 7 Enable Alarm Mode EALA 8 Enable Test Mode EtSt 9 Enable Configuration Mode ECon 10 Enable Calibration Mode ECAL 11 Enable Manual Control ESby 12 Setpoint Ramp Rate Enable ESPr 13 Enable Communications ECo 14 Password Change CodE 56 AVAILABLE
SECTION 11: PRE-TUNE MODE 11.1 Pre-Tune Mode Description The Pre-Tune Mode may be used to set the instrument's PID parameters to values which are approximately correct, in order to provide a base from which the Auto Tune Mode may optimize tuning. To engage the Pre-Tune Mode, with the instrument in Control Mode, press the SCROLL key until Mod is displayed. Press the DOWN key. Press the SCROLL key until Pre is displayed. Press the UP key until the AT LED flashes.
58
SECTION 12: AUTOTUNE MODE 12.1 AutoTune Mode and Description The Auto-Tune Mode is used to optimize tuning while the instrument is operating. To access the Auto-Tune Mode, with the instrument in Control Mode, enter the Setup Mode. Press the SCROLL key until Auto is displayed. To engage Auto-Tune, press the UP key. The AT LED will light red.
New instruments supplied by the factory contain PID terms set at "DEFAULT" values which have been found to give adequate and safe control over a wide range of applications. In the "Pre-Tune" mode of operation, the "default" PID terms are loaded and the controller demands 100% power until the process value has moved approximately halfway to the setpoint. At that point, power is removed thereby introducing a deviation oscillation.
SECTION 13: RaPID FEATURE 13.1 RaPID Description The RaPID (Response assisted PID) range of controllers have been designed with a unique "fuzzy" logic algorithm which dramatically reduces overshoot and improves settling times on start-up, setpoint changes and disturbances by 70%, without complicating set-up and usage. The fuzzy logic based algorithm enhances the traditional PID function, continuously reblending the P, I and D control building blocks on line.
62
APPENDIX A: BOARD LAYOUT - JUMPER POSITIONING FIGURE A-1 OUTPUT 2, OUTPUT 3 REMOVAL 63
FIGURE A-2 CPU PWA 64
FIGURE A-3 PSU PWA WITH RELAY OR SSR OUTPUT 1 65
FIGURE A-4 PSU PWA WITH DC OUTPUT 1 66
FIGURE A-5 OPTION PWA DC OUTPUT 2/OUTPUT 3 67
FIGURE A-6 JUMPER PLACEMENT FOR REMOTE INPUT TYPE 68
APPENDIX B: RANGE CODES The input ranges available (selectable via the front panel) are: For Thermocouple Inputs TYPE INPUT RANGE R R S S J J J J J J T T T T K 0 - 1650°C 32 - 3002°F 0 - 1649°C 32 - 3000°F 0.0 - 205.4°C 32.0 - 401.7°F 0 - 450°C 32-842°F 0 - 761°C 32 - 1401 °F -200 - 262°C -328 - 503°F 0.0 - 260.6°C 32.0 - 501.
For DC Inputs Note: Input conditioning jumper LJ1, LJ2. or LJ3 needs to be changed, see Appendix A.
APPENDIX C: RaPID CONTROL FEATURE The RaPID (Response - assisted PID) feature offers dramatic improvements in control quality compared with conventional PID techniques. It responds much more effectively than PID techniques to load conditions. With this feature, the instrument's response at start-up, during setpoint changes and during disturbances shows considerably reduced overshoot and much more shorter settling times (see below). RaPID works best with well-tuned terms.
In conditions of frequent change in load characteristics, it is recommended that the Auto-Tune facility is used. Note: With Auto-Tune and RaPID engaged together, Auto-Tune is suspended until RaPID is disengaged, whereupon Auto-Tune will operate automatically.
APPENDIX D: SPECIFICATIONS Input Specifications General Input Sample Rate: Input Resolution: Input Impedance: Isolation: Thermocouple Inputs Thermocouple Types: Calibration: Sensor Break Protection: RTD and DC mV Inputs Type and Connection: Calibration: Lead Compensation: RTD Sensor Current: Sensor Break Protection: DC mA and DC V Inputs Scale Range Maximum: Scale Range Minimum: Minimum Span: Sensor Break Protection: Four per second 14 bits approximately Greater than 100M ohm resistive (except for DC m
Dual Setpoint Selection Input Type: Voltage Free Operations: TTL Levels: Voltage free or TTL compatible Connections to contacts of external switch or relay; contacts open equal Setpoint 1 selected (minimum contact resistance = 5K ohms), contacts closed equal setpoint 2 selected (maximum contact resistance = 50 ohms) To select Setpoint 1: -0.6V to 0.8V To select Setpoint 2: 2.
To Select Remote Setpoint/ Setpoint 1: Minimum contact resistance (open): Minimum voltage for (TTL) for " 1 ": Maximum voltage for "1”: Maximum input delay (OFF-ON): Minimum input delay (ON-OFF): Isolation: 5K ohms 2.0 V 24.0 V 0.5 seconds 0.5 seconds 240 VAC isolation from all setpoints and inputs except Remote Setpoint Output Specifications Output 1 General Types Available: Relay (as standard), SSR Driver and DC as options.
Output 2 General Types Available: Relay, SSR and DC Relay Contact Type: Rating: Lifetime: Isolation: Single pole double throw (SPDT) 2A resistive at 120/240V AC > 500,000 operations at rated voltage/current Inherent SSR Driver/TTL Drive Capability: Isolation: SSRD>4.
DC Resolution: Eight bits in 250 mS (10 bits in 1 second typical, >10 bits in >1 second typical). Update Rate: Four times per second Ranges: 0-20 mA, 4-20 mA, 0-10 V, and 0-5 V NOTE: Changes between V and mA ranges also require jumper movement. Load Impedance: 0 - 20 mA: 500 ohm maximum 4 - 20 mA: 500 ohm maximum 0 - 10 V: 500 ohm minimum 0 - 5V: 500 ohm minimum Isolation: Isolated from all other inputs and outputs.
Alarms Maximum Number: Maximum # Outputs: Combination Alarms: Hysteresis: Loop Alarm: Performance Reference Conditions Ambient Temperature: Relative Humidity: Supply Voltage: Source Resistance: Lead Resistance: Two "soft" alarms plus Loop Alarm* Up to 2 outputs can be used for alarm purposes Logical OR or AND of alarms to an individual hardware output is available.
DC Outputs Output 1 Accuracy: mA: V: Output 2 Accuracy: mA: V: Output 3 Accuracy: (Recorder Accuracy) mA: V: 0 - 20mA ± 0.5% of span (20 mA) @250 ohm 4 - 20mA ± 0.5% of span (16 mA) @ 250 ohm 0 - 10V ± 0.5% of span (10 V) @ 2K ohm 0 - 5V ± 0.5% of span (5 V) @ 2K ohm 0 - 20mA ± 0.5% of span (16 mA) @250 ohm 4 - 20mA ± 0.5% of span (16 mA) @ 250 ohm 0 - 10V ± 0.5% of span (10 V) @ 2K ohm 0 - 5V ± 0.5% of span (5 V) @ 2K ohm 0 - 20mA ± 0.5% of span (20 mA) @250 ohm 4 - 20mA ± 0.
Performance Under Operating Conditions Temperature Stability: Cold Junction Compensation (thermocouple only): Supply Voltage Influence: Relative Humidity Influence: Sensor Resistance Influence: 0.01 % of span /degree C change in ambient temperature Better than ± 1º C Note: Thermocouple must not be grounded! Damage to the cold junction in the control will result! Negligible Negligible Thermocouple 100 ohm: <0.1 %of span error Thermocouple 1000 ohm: < 0.5% of span error RTD Pt100 50 ohm/lead: 0.
APPENDIX E: SOFTWARE REFERENCE SHEET Tune Parameter LSP rSP SP1 SP2 iCor Po1 Po2 Pb1 Pb2 ArSt rAtE rSEt HyS1 HyS2 SPrd SPrr rSPo Ct1 Ct2 Setting 81
Alarm Parameter ALA1 ALA2 Inhi (Alm 1 Value) AHy1 (Alm 2 Value) AHy2 LAEn LAti Setting Enable Parameter ESP EPrE EAut ErAP EPtn Etun EALA Etst ECon ECAL ESby ESPr ECo Code Setting 82
Configuration Parameter InPS FiLt rinP CtL1 USE2 USE3 CbS CPAr CAd CJC dPoS Euu EuL SPuL SPLL rSPu rSPL o1PL Pou PoL Setting Hardware Definition dEFn OPtn 2inp Setting 83
APPENDIX F: FLOW CHART OF OPERATION 84
APPENDIX G: MODEL NUMBER MATRIX 85
86
87