Owner's manual

25
SECTION 7: SET-UP MODE
To enter the Set-Up mode, press and release the SCROLL key until SEt is displayed.
Use the DOWN key to enter the Set-Up mode. The “S” LED will light. Depress and
release the SCROLL key to sequence through the parameters and their values,
alternately showing the parameter code in the lower display with the upper display
blank, then the parameter code with the parameter values in the upper display. Use the
UP and DOWN keys to adjust the parameter values. After adjusting a parameter,
depress the SCROLL key to proceed to the next parameter. The DOWN key may also
be used to advance to the next parameter when a parameter code is showing in the
lower display and the upper display is blank.
To exit the Set-Up mode, press the UP key whenever a parameter code is displayed in
the lower display and the upper display is blank.
Table 7-1 Set-Up Mode Parameters
STEP DESCRIPTION DISPLAY
CODE
AVAILABLE SETTINGS FACTORY
SETTING
1 Alarm Status
3
ALSt Read Only
2 Maximum Hold HiHd Read Only
3 Minimum Hold LoHd Read Only
4 Time Exceeded tLE Read Only
5 Input Correction iCOR +/-Span 0
6 Input Filter Filt 0.0 to 100.0 seconds in
.5 sec. Increments
2.0
7 Hysteresis Limit HySt 0 to 10.0% of span 1
8 Process Output Upper Pou -1999 to 9999 Span Max.
9 Process Output Lower PoL - 1999 to 9999 Span. Min.
10 Process High Alarm 1
1
PHA1 ± Span Span Max.
11 Process Low Alarm 1
1
PLA1 ± Span Span Min.
12 Process High Alarm 2
1
PHA2 ± Span Span Max.
13 Process Low Alarm 2
1
PLA2 ± Span Span Min.
14 Decimal Position dPoS 0, 1, 2, 3 1
15 Engineering Units
2
Upper
Euu -1999 to 9999 1000
16 Engineering Units
2
Lower
EuL - 1999 to 9999 0
17 Comm. Enable CCon O=Disable
1 =Enable
1