Owner's manual

23
Table 6-1 Configuration Mode Parameters
STEP DESCRIPTION DISPLAY
CODE
AVAILABLE SETTINGS FACTORY
SETTING
1 Input Range
Select
inPS See App. C* 1420
2 Limit Action ACt Hi/Lo/Both Hi
3 Limit Maximum SPUL +/- SPAN Span max.
4 Limit Minimum SPLL +/- SPAN Span min.
5 Alarm 1 Type ALA1 nonE = No Alarm
P_hi = Process High
P_Lo = Process Low
LiHi = High Limit
LiLo = Low Limit
P_hi
6 Alarm 2 Type ALA2 Same selection as ALA1 P_hi
7 Output 2 Usage
2
USE2 AL_d = Alm1 Direct
LA_r = Annunc. Reverse
LA_d = Annunc. Direct
Ad_r =Rev Logic AND
Ad_d=Dir Logic AND
Or_r =Rev Logic OR
Or_d=Dir Logic OR
A2_r = Alm Rev
A2_d = Alm Dir
Al_r = Alm1 Rev
Al_d
8 Output 3 Usage
2
USE3 Al-d =Alm Dir
rEcP = Rcdr Out P.V.
LA_r = Annunc. Reverse
LA_d = Annunc. Direct
Ad_r = Rev Logic AND
Ad_d = Dir Logic AND
Or_r = Rev Logic OR
Or _d = Dir Logic OR
A2_r = Alm2Rev
A2_d = Alm2Dir
Al_r = Alm Rev
Al_d (rEcP
when output 3
is retransmit)
9 Com Bit Rate
3
CbS 1200, 2400, 4800, 9600 4800
10 Com Parity
3
CPAr nonE, EvEn, odd nonE
11 Com Address
3
CAd 1 - 32 1
12 CJC Enable CJC EnAb
diSA
EnAb
1 Does not appear unless Output 3 is configured as 4-20 mA.
2 Does not appear unless additional output has been selected.
3 Does not appear unless communications option has been selected.
*The Hardware Definition Code and input jumper configuration may need to be
changed. See Appendices A and B.