Manual

5
Table 2 Operating Parameter Outline
Code
Name
Settings
CtL
Control Mode
PID
At
Auto-tuning
OFF
P *
Proportional Band
5 **
I
Integral Time
120
d
Derivative Time
0
Ct
Cycle Time
1
FL
Input Filter
2
bS
PV Bias (Offset)
0
LoC
Key Lock
0
* If P is not displayed the Control Mode (CtL)
must be first set to Pid.
** For F change to value 13.
Definitions for Table 2:
CtL Control Mode - This parameter determines whether controller functions as a time
proportional or an on/off control.
At Auto-tuning Off for PID tuning, ON for controller to tune process.
P Proportional Band - Expressed in degrees. This value determines the band width on
both sides of the setpoint within which the control provides proportional control.
I Integral Time - Expressed in seconds. This parameter corrects for errors in actual
temperature versus the setpoint.
D Derivative Time - Expressed in seconds. This effect of the derivative time is in direct
proportion to the time setting.
Ct Cycle Time - Expressed in seconds. This is the total time for one ON/OFF cycle of the
controller output during the proportional action.
FL Input Filter Expressed in seconds. This function should be used when the PV may
fluctuate greatly (i.e. input signal contains noise).
bS PV Bias - Expressed in percent of span. From 100 to 100% of span, this parameter
used to set the actual oven temperature to the controller display.
LoC Key Lock - This provides levels of access to the controller.
0 = No key lock, full access to controller.
1 = Prevents changing of all parameters except setpoint.
2 = Prevents all parameters from being changed including the setpoint.
1 = Set to enter the Setup parameter setting display.
When LoC = -1, the parameters are displayed in the order shown in the Set-Up
Parameters section, below.