OPERATION MANUAL OFFICE PRO 12 / OFFICE PRO 18 / OFFICE PRO 24 READ THIS MANUAL CAREFULLY FOR INSTRUCTIONS ON CORRECT INSTALLATION AND USAGE AND READ ALL SAFEGUARDS SECCIÒN EN ESPAÑOL SECTION EN FRANÇAIS AVAILABLE AT WWW.MOVINCOOL.
© 2007 DENSO SALES CALIFORNIA, INC. All rights reserved. This book may not be reproduced or copied, in whole or in part, without the written permission of the publisher. DENSO SALES CALIFORNIA, INC. reserves the right to make changes without prior notice. MovinCool is a registered trademark of DENSO Corporation.
OPERATION MANUAL OFFICE PRO 12 / OFFICE PRO 18 / OFFICE PRO 24
Table of Contents FOREWORD................................................................................. 5 Definition of Terms ............................................................... 5 GENERAL WARNINGS & CAUTIONS ........................................ 6 Inventory ................................................................................ 7 INSTALLATION ............................................................................ 8 Choosing an Installation Site ..............................
FOREWORD Congratulations on purchasing the MovinCool portable air conditioner. This manual explains how to install and operate the MovinCool Office Pro12, Office Pro18, and Office Pro24 portable air conditioning units. Please read this operation manual thoroughly to familiarize yourself with the features of the unit and to ensure years of reliable operation. You may also find it useful to keep this operation manual on hand for reference.
GENERAL WARNINGS & CAUTIONS 1) All electrical work, if necessary, should only be performed by qualified electrical personnel. Repair to electrical components by non-certified technicians may result in personal injury and/or damage to the unit. All electrical components replaced must be genuine MovinCool parts, purchased from an authorized reseller. 2) The proper electrical outlet for MovinCool units must be equipped with a UL approved circuit breaker.
INVENTORY After unpacking your MovinCool unit, please check to make sure you have the following items : 1) Office Pro 12 or Office pro 18 or Office Pro 24 MovinCool Unit (1) 2) Operation Manual/Product Registration (1) NOTE : If any of these items were not included in the box or appear damaged, please contact your MovinCool reseller for replacement.
INSTALLATION Choosing an Installation Site ! CAUTION : Following are some precautions to consider before choosing your installation site. Please review carefully as improper installation may result in personal injury or damage to the unit. 1) Do not use the unit in areas where leakage of flammable gas may occur. 2) Do not use the unit in areas where it will be exposed to rain or water. 3) Do not use the unit in an atmosphere of excessively corrosive gas or vapor.
INSTALLATION(cont.) Moving the Unit Unlock the casters and push the MovinCool unit using the side handles to a flat, level surface and set the casters back to the LOCKED position.
INSTALLATION (cont.) Plugging in the Unit 1) Check the prong and surface of the power cord plug for dust/dirt. If dust and/or dirt are present, wipe off with a clean, dry cloth. 2) Check the power cord, plug and prong for damage or excess play. If any damage or excess play is found, contact your MovinCool reseller for repair. WARNING: ! 1) If the power cord or plug is damaged, repair should only be performed by qualified electrical personnel.
INSTALLATION (cont.) Warning Signal Connection (Output Signal terminal L+ and L-)㧖 The controller is equipped with a warning signal output relay type (Form C, normal open dry contact) which can be used to monitor the failure condition. Relay contactor (not connector) is closed when the following condition has occurred : a. Tank Full b. Temperature sensor fails c.
INSTALLATION (cont.) LCDI Power Cord Instruction ! WARNING The LCDI device is non-serviceable device. Attempting to open the device may expose the user to hazardous of electric shock, and could void warranties of this product. Manufacturer’s reliability is limited to the replacement of the device. ! CAUTION 1. Read the attention print on the device for proper use and handling of this device. 2. This device is used for monitoring leakage current. 3. Do not immerse in water. 4.
FEATURES For all models: 1) A digital electronic control panel, which allows the user to control the unit’s operation easily. 2) Dual fan speeds (either HIGH or LOW) in both COOL and Fan Only modes. 3) Digital LCD display with blue backlight that indicates: a. Clock with day and time. b. Room Temperature and Set Point Temperature (either Fahrenheit or Celsius). c. Fan Speed Status d. Cool Mode Status e. Program Start time and Stop time f. Program Run and Stop g. Status Codes h.
OPERATION Control Panel Before operating the unit, it is important to familiarize yourself with the basic controls located on the control panel. PROGRAM MO TU WE TH FR SA SU AM START STOP CLOCK PROGRAM ON LOCKED PM F C HI LO ON COOL OFF FAN RUN/ STOP F C SET TEMP PROGRAMMING ROOM TEMP SET PROG 8 7 6 TANK FULL FAN MODE 2 SET CLOCK HI/LO 5 SET TEMP COOL MODE 1 ON/OFF ENTER 4 3 1) COOL Mode Button Activates/deactivates the COOL mode/turns the unit off.
OPERATION (cont.) Control Panel (Cont.) LCD Indicators 9 11 12 14 15 16 13 19 10 17 18 9) MO...SU ޓޓޓIlluminates to indicate selected day ޓޓޓof the week 10) °C or °F Temperature displayed in either Fahrenheit or Celsius (See Note) 11) AM/PM Illuminates to indicate AM or PM time of day. 12) PROGRAM Blinking during program editing mode. 13) PROGRAM ON Illuminates to indicate program is running. 14) START Illuminates to indicate program start time.
OPERATION (cont.) Set Clock Prior to operating the Office Pro 12, 18, or 24 users should set the clock of the controller to the correct time as shown in the following steps : 1) Press and hold the SET CLOCK button for 3 seconds or until beep. (LCD will indicate blinking “CLOCK” and blinking “Day of the week ”) AM HI LO ON COOL OFF PROGRAM PM ON LOCKED F C FAN 2) Press SET TEMP buttons to select day of the week.
OPERATION (cont.) How to Set a Program SET START TIME 1) Press and hold the “SET PROG” button for 3 seconds or until beep. 2) Press “SET TEMP” buttons to select day of the week. PROGRAM MO TU WE TH FR SA SU AM START STOP CLOCK HI FAN LO ON COOL OFF PROGRAM PM ON LOCKED F C RUN/ STOP F C SET TEMP PROGRAMMING ROOM TEMP SET PROG Step 1 & 18 TANK FULL 3) Press “ENTER” button. FAN MODE SET CLOCK HI/LO 4) Press “SET TEMP” buttons to select desired hour. 5) Press “ENTER” button.
OPERATION (cont.) How to View and Delete Program 1) Press and hold the SET PROG button for 3 seconds or until beep. 2) To view edited program - While pressing and holding the SET PROG button, press SET TEMP ( / ) to scroll program sequence. 3) To delete a program - Press ENTER and SET PROG buttons once simultaneously. 4) To delete multiple program - Press and hold ENTER and SET PROG buttons simultaneously.
OPERATION (cont.) Operating Modes The Office Pro 12, Office Pro 18, and Office Pro 24 can be operated in two modes, Fan Only and COOL. When in Fan Only mode, the unit circulates the surrounding air. When in COOL mode, the compressor is operational and cool air is circulated. 1) COOL Mode Once the compressor has been disengaged for more than 120 seconds, the unit will operate in Fan Only mode for approximately 5 seconds before the compressor re-engages.
OPERATION (cont.) Empty the Drain Tank During COOL mode, condensate will accumulate in the drain tank. When the drain tank becomes full, the FULL TANK LED will flash and the LCD displays “Tank FL” and the ALARM signal output is turned ON * and the unit will shut off automatically. NOTE : If you want to empty the drain tank, while the unit is in operation, press the COOL ON/OFF button to turn the unit off. * Not available for OP 12 model 1) Open the drain tank door.
OPERATION (cont) Drain Pump Kit (Optinal) A drain pump kits are available to allow continuous operation and to eliminate the need for a drain tank. When the water collects to level (A) in the pump reservoir, the drain pump begins to operate and discharge the water. NOTE : The compressor will not operate while the drain pump is discharging in water for the Office Pro 12 and Office Pro 18. When the water level drops below level (B), the drain pump stops, and the compressor will restart.
TROUBLESHOOTING Self-Diagnostic Codes Self-Diagnostic Codes will be displayed on the Control Board under the following conditions: LCD Display Codes Condition When the drain tank switch shuts off the unit LCD displays “TANK FL” and FULL TANK LED flashes. Once emptying the drain tank procedure is completed and “ON/OFF” has been pushed, unit will return to normal operation. When the drain pump malfunctions, the compressor will shut off, and LCD will display “AS”.
DAILY INSPECTION & MAINTENANCE Empty the Drain Tank To empty the drain tank, refer to instruction on page 20. Clean the Air Filters Clean the air filters once a week. If the unit is used in a dusty environment, more frequent cleaning may be required. A dirty air filter can reduce air output resulting in a decrease of the cooling capacity. Filter Removal Method 1) Turn the unit off by pressing the COOL ON/OFF button. If a program is running, you must first press the Program “RUN” button.
DAILY INSPECTION & MAINTENANCE (cont.) Filter Cleaning Method FI LTER 1) Remove dust from the element with a vacuum cleaner, or rinse in cold or lukewarm water. If the element is extremely dirty, wash with a neutral detergent. 2) After the element has been cleaned, rinse with clean running water, allow to dry, then reinstall. In-Season/Off-Season Inspection & Maintenance In-Season 1) Check the prongs and surface of the power cord plug for dust and/or dirt.
TROUBLESHOOTING Check the following items before calling a qualified technician SYMPTOM Unit does not operate POSSIBLE CAUSE 1) Ground fault breaker trip or LCDI power cord trip. Reset Breaker or Reset power cold 2) Drain Tank is full (Tank Full LED will be flashing) Empty the drain tank 3) High Pressure Activated 10 times in 24hours. Insufficient Cooling REMEDY 1) Clean air filter.
TECHNICAL SPECIFICATIONS ITEMS/FEATURES Rating Conditions Dry bulb Wet bulb Humidity ITEMS/FEATURES Specification Power frequency Line voltage Power consumption Current consumption Power factor Starting current Power wiring Cooling Unit Cooling capability Cooling system Blower Type of fan Air volume:Evaporator(High speed) Condenser(High speed) Motor output (High) (Low) Compressor Type Output Refrigerant Type Refrigerant Capacity Safety Devices Compressor overload protector Fan moter protector Anti-freezing
THE #1 SPOT COOLING SOLUTION .+/+6'& 9#44#06; DENSO SALES CALIFORNIA, INC. (“DENSO”) warrants its MOVINCOOL Products only to the extent stated in its official written warranties.