Specifications
[Issue No.] GOT-A-0064-C [Page] 29/39
[Title] List of Valid Devices Applicable for GOT2000 Series
[Date of Issue] Ver. C: February 2015 (First Edition: September 2013)
[Relevant Models] GOT2000 Series
HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
NAGOYA WORKS : 1-14, YADA-MINAMI 5-CHOME, HIGASHI-KU, NAGOYA, JAPAN
TECHNICAL BULLETIN
(3) RS-232 cable connection diagram for a V620 RFID controller manufactured by OMRON Corporation
The following shows connection cables that must be produced by the user.
Maximum cable length: confirm with the RFID controller manufacturer.
RFID controller
Cable connection and signal direction
GOT
Signal name Pin No. Pin No. Signal name
FG 1
1 CD
SD 2 2 RD(RXD)
RD 3 3 SD(TXD)
RS 4 4 DTR(ER)
CS 5 5 SG
-
6 6 DSR(DR)
SG 7 7 RS(RTS)
-
8 8 CS(CTS)
ER 20 9 NC
*For the cables between and , refer to the manual created by OMRON Corporation
(4) RS-232 cable connection diagram for an ICU-60S RFID controller manufactured by MARS TOHKEN
SOLUTION CO.LTD.
The following shows connection cables that must be produced by the user.
Maximum cable length: confirm with the RFID controller manufacturer.
RFID controller (ICU-60S)
Cable connection and signal direction
GOT
Signal name Pin No. Pin No. Signal name
+24V 1
1 CD
GND 2 2 RD(RXD)
TXD 3 3 SD(TXD)
RXD 4 4 DTR(ER)
CTS 5 5 SG
RTS 6 6 DSR(DR)
/RST 7 7 RS(RTS)
GND 8 8 CS(CTS)
-
9 9 NC
*For the cables between and , refer to the manual created by MARS TOHKEN SOLUTION CO.LTD..