User Guide

ELECTRICAL SYSTEM
15
1. Basic Operation of Classic Plus 26 Electrical Circuit
There are two basic components used to control the operation of the Classic Plus 26 Electrical System:
Control Panel Assembly
Control Box
The Control Panel Assembly contains the Control Panel, Control Board (with inputs for the freeze and
room temperature thermistors), drain switch, and a microprocessor.
A. Fan Only Mode
Low Fan Mode - When the Low Fan Mode button on the control panel is pressed, the microprocessor
turns on the buttons LED and activates the Fan On Relay (Relay Board), sending line voltage (208/230
VAC) to the N.C. (Normally Closed) contacts of the fan mode relay. This output is connected to the J5
terminal (relay board) where the LOW SPEED wire of the fan motor is connected.
High Fan Mode When the High Fan Mode button on the control panel is pressed, the microprocessor
turns on the buttons LED and activates both the Fan On Relay and Fan Mode Relay. This sends line
voltage (208/230 VAC) from the Fan On Relay to the N.O. (Normally Open) contacts of the Fan Mode
Relay. This output is connected to the J6 terminal (Relay Board) where the HIGH SPEED wire of the Fan
Motor is connected.
B. Cool Mode - In Addition to Fan Only Mode (as described above)
When the Cool On/Off button on the control panel is pressed, the microprocessor turns on the buttons
LED and if the Temperature Set Point is less than the current room temperature, activates the Compres-
sor Relay (Relay Board). This sends line voltage (208/230 VAC) to the J4 terminal (Relay Board) where the
wire from the Compressor wire harness is connected.