Technical data

June 2005
CAT.02.02.S.K.CD For more information visit: www.EatonElectrical.ca
71
XT IEC Power Control
Contactors, Starters and Overload Relays
Technical Data and Specifications
Table 109. AC Ratings (Continued)
At maximum permissible ambient temperature.
Example —
The transformer has a nominal current of 10A with an inrush current of 18 times the nominal current. So, the contactor must have an AC-3 current of
18/6 x 10A = 30A. Using an XTCE032C (32A AC-3) contactor is recommended.
Description XTCE040D XTCE050D XTCE065D XTCE080F XTCE095F XTCE115G XTCE150G
AC-1 Operation
Conventional Free Air Thermal Current,
3-Pole, 50 – 60 Hz
at 40°C (I
th
)
at 50°C (I
th
)
at 55°C (I
th
)
at 60°C (I
th
)
60A
57A
55A
50A
70A
65A
63A
60A
85A
80A
75A
72A
130
110
130
110
190
160
190
160
Conventional Free Air Thermal Current,
1-Pole (I
th
)
125A 150A 180A
AC-3 Operation
Rated Operational Current, 50/60 Hz
(I
e
)
in amperes
220/230V
240V
380/400V
415V
440V
500V
660/690V
1000V
40
40
40
40
40
40
25
50
50
50
50
50
50
32
65
65
65
65
65
65
37
80
80
80
80
80
80
65
95
95
95
95
95
95
80
115
115
115
115
115
115
110
150
150
150
150
150
150
132
Rated power (P) in kilowatts
220/230V
240V
380/400V
415V
440V
500V
660/690V
1000V
12.5
13.5
18.5
24
25
28
23
15.5
17
22
30
32
36
30
20
22
30
39
41
47
35
25
37
58
63
30
45
70
75
37
55
85
105
48
75
110
125
AC-4 Operation
Rated Operational Current, 50/60 Hz
(I
e
)
in amperes
220/230V
240V
380/400V
415V
440V
500V
660/690V
1000V
18
18
18
18
18
18
14
21
21
21
21
21
21
17
25
25
25
25
25
25
20
37
37
37
37
37
37
27
15
40
40
40
40
40
40
37
17
55
55
55
55
55
55
45
22
65
65
65
65
65
65
50
25
Rated power (P) in kilowatts
220/230V
240V
380/400V
415V
440V
500V
660/690V
1000V
5
5.5
9
9.5
10
11
12
6
6.5
10
11
12
13
14
7
7.5
12
13
14
16
17
11.5
13
19
22
23
27
26
22
13
14
20
24
26
29
36
25
17
19
28
33
35
40
45
32
20
23
34
39
41
47
48
37
AC-6A Operation
Transformer Loads Values are application specific. Calculation is I
e
AC-3
= X / 6 * I
e Transformer where X is the inrush current of the
transformer and
I
e Transformer is the nominal current.
AC-6B Operation
Capacitor Loads
Individual compensation rated operational cur-
rent I
e
of three-phase capacitors in amperes
Up to 525V
690V
Maximum inrush current peak (x I
e
)— — — — — —
Component Lifesaving (Operations) — — — — — — —
Maximum Operating Frequency (ops/hr) — — — — — — —