Technical data
Table Of Contents

June 2005
64
For more information visit: www.EatonElectrical.ca CAT.02.02.S.K.CD
XT IEC Power Control
Contactors, Starters and Overload Relays
Technical Data and Specifications
Frames F – G
Table 105. Coil Data — Frames F – G
At 24V: 0.7 – 1.3 without additional auxiliary contact modules and ambient temperature
+40°C [104°F].
XTCE80F XTCE95F XTCE115G XTCE150G
Voltage Tolerance
Pick-Up (x U
c
)
AC operated
DC operated
Drop-Out (x U
c
)
AC operated
DC operated
0.8 – 1.1
0.7 – 1.2
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.7 – 1.2
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.7 – 1.2
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.7 – 1.2
0.3 – 0.6
0.15 – 0.6
Power Consumption of the coil at cold state and 1.0 x U
c
AC operated
Pick-Up VA
Pick-Up W
310
165
310
165
130
130
130
130
Single-voltage coil 50 Hz
Sealing VA
Sealing W
26
5.5
26
5.5
3.5
2
3.5
2
60 Hz
Pick-Up VA
Pick-Up W
Sealing VA
Sealing W
375
190
31
6.8
375
190
31
6.8
130
130
3.5
2
130
130
3.5
2
50/60 Hz
Pick-Up VA
Pick-Up W
Sealing VA
Sealing W
375
190
31
6.8
375
190
31
6.8
130
130
3.5
2
130
130
3.5
2
DC operated
Pick-Up W
Sealing W
90 at 24V
2 at 24V
90 at 24V
2 at 24V
130 at 24V
2 at 24V
130 at 24V
2 at 24V
Duty Factor (%DF) 100 100 100 100
Switching Time at 100% U
c
(approximate values)
Main Contact
AC operated
Closing delay (mS)
Opening delay (mS)
DC operated
Closing delay (mS)
Opening delay (mS)
Max. 25 mS
Max. 20 mS
Max. 40 mS
Max. 40 mS
Max. 25 mS
Max. 20 mS
Max. 40 mS
Max. 40 mS
Max. 30 mS
Max. 40 mS
Max. 35 mS
Max. 40 mS
Max. 30 mS
Max. 40 mS
Max. 35 mS
Max. 40 mS
Electromagnetic Compatibility (EMC)
Emitted interference To EN60947-1
Noise Immunity To EN60947-1