Technical data

June 2005
CAT.02.02.S.K.CD For more information visit: www.EatonElectrical.ca
63
XT IEC Power Control
Contactors, Starters and Overload Relays
Technical Data and Specifications
Coil Data
Frame B – D
Table 104. Coil Data — Frame B – D
At 24V: 0.7 – 1.3 without additional auxiliary contact modules and ambient temperature +40°C [104°F].
Coil Suffix AD: U
min
110V DC/U
max
130V DC.
Coil Suffix BD: U
min
200V DC/U
max
240V DC.
Example:
U
c
= 0.7 x U
min
— 1.2 x U
max
U
c
= 0.7 x 24V — 1.2 x 27V DC
XTCE007B XTCE009B XTCE012B XTCE015B XTCE018C XTCE025C XTCE032C XTCE040D XTCE050D XTCE065D
Voltage Tolerance
Pick-Up (x U
c
)
AC operated
DC operated
Drop-Out (x U
c
)
AC operated
DC operated
0.8 – 1.1
0.8 – 1.11
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.11
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.11
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.11
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.11
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.11
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.11
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.11
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.11
0.3 – 0.6
0.15 – 0.6
0.8 – 1.1
0.8 – 1.11
0.3 – 0.6
0.15 – 0.6
Power Consumption of the coil at cold state and 1.0 x U
c
AC operated
Pick-Up VA
Pick-Up W
24
19
24
19
24
19
24
19
50
40
50
40
50
40
130
80
130
80
130
80
Single-voltage coil 50 Hz
Sealing VA
Sealing W
4
1.2
4
1.2
4
1.2
4
1.2
8
2.4
8
2.4
8
2.4
14
4
14
4
14
4
60 Hz
Pick-Up VA
Pick-Up W
Sealing VA
Sealing W
29
23
4.4
1.3
29
23
4.4
1.3
29
23
4.4
1.3
29
23
4.4
1.3
62
50
9.1
2.7
62
50
9.1
2.7
62
50
9.1
2.7
62
50
9.1
2.7
62
50
9.1
2.7
62
50
9.1
2.7
50/60 Hz
Pick-Up VA
Pick-Up W
Sealing VA
Sealing W
28
26
22
21
4.6
3.9
1.4
1.2
28
26
22
21
4.6
3.9
1.4
1.2
28
26
22
21
4.6
3.9
1.4
1.2
28
26
22
21
4.6
3.9
1.4
1.2
60
54
48
43
9.5
7.9
2.8
2.4
60
54
48
43
9.5
7.9
2.8
2.4
60
54
48
43
9.5
7.9
2.8
2.4
60
54
48
43
9.5
7.9
2.8
2.4
60
54
48
43
9.5
7.9
2.8
2.4
60
54
48
43
9.5
7.9
2.8
2.4
DC operated
Pick-Up W
Sealing W
3
3
3
3
4.5
4.5
4.5
4.5
12 at 24V
0.5 at 24V
12 at 24V
0.5 at 24V
12 at 24V
0.5 at 24V
12 at 24V
0.5 at 24V
12 at 24V
0.5 at 24V
12 at 24V
0.5 at 24V
Duty Factor (%DF) 100 100 100 100 100 100 100 100 100 100
Switching Time at 100% U
c
(approximate values)
Main Contact
AC operated
Closing delay (mS)
Opening delay (mS)
DC operated
Closing delay (mS)
Opening delay (mS)
<20
<15
<35
<15
<20
<15
<35
<15
<20
<15
<35
<15
<20
<15
<35
<15
<25
<20
<55
<15
<25
<20
<55
<15
<25
<20
<55
<15
<25
<25
<60
<20
<25
<25
<60
<20
<25
<25
<60
<20
Arcing time (mS) 10 10 10 10 10 10 10 10 10 10
Electromagnetic Compatibility (EMC)
Emitted interference To EN-60947-1
Noise Immunity To EN-60947-1