Technical data
Table Of Contents

June 2005
60
For more information visit: www.EatonElectrical.ca CAT.02.02.S.K.CD
XT IEC Power Control
Contactors, Starters and Overload Relays
Technical Data and Specifications
Table 101. XT Contactors Technical Data and Specifications — Frame L – M (Continued)
When using contactors for group compensation, a minimum inductance of approx. 6 uh per capacitor must be available to limit the high inrush current
peaks. This corresponds to an air-cored coil with 5 windings and a coil diameter of approximately 140 mm. The conductor cross-section must be
selected according to the rated current per phase.
Description XTCE185L XTCE225L XTCE250L XTCE300M XTCE400M XTCE500M
General (Continued)
Mounting Position,
AC and DC Operated
Ambient Temperature -25 to 60°C
[-13 to 140°F]
-25 to 60°C
[-13 to 140°F]
-25 to 60°C
[-13 to 140°F]
-25 to 60°C
[-13 to 140°F]
-25 to 60°C
[-13 to 140°F]
-25 to 60°C
[-13 to 140°F]
Ambient Storage Temperature -40 to 80°C
[-40 to 176°F]
-40 to 80°C
[-40 to 176°F]
-40 to 80°C
[-40 to 176°F]
-40 to 80°C
[-40 to 176°F]
-40 to 80°C
[-40 to 176°F]
-40 to 80°C
[-40 to 176°F]
Environmental
Mechanical Shock
Resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock 10 mS
Main contact — NO Contact
Auxiliary contact — NO Contact
Auxiliary contact — NC Contact
10g
10g
8g
10g
10g
8g
10g
10g
8g
10g
10g
8g
10g
10g
8g
10g
10g
8g
Overvoltage Category/
Pollution Degree
III/3 III/3 III/3 III/3 III/3 III/3
Switching Capacity, kvar
Individual Compensation
230V
400/420/440V
525V
690V
87
150
190
150
—
—
—
—
—
—
—
—
115
200
265
200
—
—
—
—
—
—
—
—
Group Compensation,
with Choke
230V
400/420/440V
525V
690V
80
150
200
260
100
175
230
300
110
190
260
340
130
225
290
390
160
280
370
480
160
280
370
480
Group Compensation,
without Choke
230V
400/420/440V
525V
690V
66
115
145
115
—
—
—
—
—
—
—
—
85
150
195
150
—
—
—
—
—
—
—
—
180°
30° 30°
90°
90°
30° 30°
90° 90°