Technical data
Table Of Contents

June 2005
16
For more information visit: www.EatonElectrical.ca CAT.02.02.S.K.CD
XT IEC Power Control
Miniature Controls
Product Selection
Star-Delta (Wye-Delta) Miniature Contactors
Table 22. Star-Delta (Wye-Delta) Miniature Contactor Configuration
Operating Frequency: 30 Starts/hour
Underscore (_) indicates magnet coil suffix required. See Table 24.
Figure 13. Star-Delta (Wye-Delta) Power
Wiring Diagram
Table 23. Mini Overload Relay Settings (A)
Note: Depending on the coordination type required (i.e. Type 1 or Type 2) it must be established whether the fuse protection and the input wir-
ing for the main and delta contactors are to be common or separate.
Table 24. Magnet Coil Suffix
For indicated coils, price adder of 10% must be applied to the contactor list price in Table 22.
With DC Operation: Integrated diode resistor combination, coil rating 2.6W.
Maximum kW Ratings AC-3 Maximum 3-Phase Current Motor Rating Max.
Changeover
Time (sec.)
Spare
Auxiliary
Contacts
Component Catalog Number Price
3-Phase Motors 50 – 60 Hz 1-Phase hp
Ratings
3-Phase hp Ratings Description Catalog Number
220/230/
240V
380/400/
440V
500V 115V 200V 230V 200V 230V 460V 575V K1M AC DC
4 5.5 5.5 1/2 1 1-1/2 2357-1/2 30 K1M Main
Contactor
XTMC9A10_
K1M Auxiliary
Contact
XTMCXFC22
K5M Delta
Contactor
XTMC9A01_
K3M Star
Contactor
XTMC9A10_
K3M Auxiliary
Contact
XTMCXFC02
K1T Timing
Relay
XTTR6A60S51B
21
22
31
32
53
54
K1M
5
642
31
K5M
5
642
31
K3M
642
351
U1
V1
W1
M1
3
M1
V2
W2
U2
A
C
B
Setting Starting
A: I
N
x 0.58 ≤ = 15 sec
Motor Protection in the Y and Delta
Configurations.
B: I
N
x 1 15 – 40 sec
Only partial motor protection in star position
C: I
N
x 0.58 > 40 sec
Motor not protected in star position.
Timing Relay set to approximately 10 sec.
Coil Voltage Suffix
Code
Coil Voltage Suffix
Code
Coil Voltage Suffix
Code
Coil Voltage Suffix
Code
110V 50 Hz, 120V 60 Hz A 415V 50 Hz, 480V 60 Hz C 400V 50 Hz N 120V DC AD
220V 50 Hz, 240V 60 Hz B 550V 50 Hz, 600V 60 Hz D 380V 60 Hz P 220V DC BD
230V 50 Hz F 208V 60 Hz E 12V 50/60 Hz R 12V DC RD
24V 50/60 Hz T 190V 50 Hz, 220V 60 Hz G 24V 50 Hz U 48V DC WD
24V DC TD
240V 50 Hz, 277V 60 Hz H 42V 50 Hz, 48V 60 Hz W ——
——380V 50 Hz, 440V 60 Hz L 48V 50 Hz Y ——
Overload Relays. . . . . . . . . . . . . . . . . . . . . . . Page 17
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . Page 18
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . Page 27
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . MC8