Technical data

June 2005
160
For more information visit: www.EatonElectrical.ca CAT.02.02.S.K.CD
XT IEC Power Control
Combination Motor Controllers
Product Family Overview
Standards and Certifications
UL 508 Type F Combination Motor
Controller
IEC Type 2 Approved per
IEC 60947-4-1
UL Listed File No. E218618
CE Mark
Protection in Different Controller
Types
A UL 508 Type E Self-protected Manual
Combination Starter/Motor Controller
consists of a single device having inte-
gral short circuit protection, a main set
of contacts, motor overload protec-
tion, and may also include a UL listed
Line Side Adapter (See Table 209). This
type of controller is a legitimate short
circuit protective device and discon-
nect means for the downstream motor.
It does require an upstream feeder
short circuit protective device, but
does not require a dedicated branch
circuit protection or a disconnect
means if used with a Line Side
Adapter. A UL 508 Type E rating means
that the unit clears a fault and does not
experience any welding of the power
poles. A UL 508 Type E self-protected
manual motor controller will remain
fully functional should a short circuit
within its ratings occur. E.g. XTPR.
An XT UL 508 Type F Self-protected
Combination Motor Controller consists
of a UL Listed Type E Self-protected
Manual Combination Starter/Motor
Controller, a UL Listed Contactor, and
a UL Listed Line Side Adapter (See
Table 209). While the UL 508 Type E
self-protected manual motor controller
of this combination motor controller
device is a legitimate short circuit
protective device and disconnect
means for the downstream motor,
the contactor is not “self-protected.”
E.g. XTFC, XTFR.
In addition, as a complete assembly or
modular components, the device
should have Type 2 Coordination certi-
fication. Type 2 Coordination means
the Starter or the Controller must
exhibit little or no damage following a
major short circuit fault and should be
able to be returned to proper service
without replacing any parts.
Table 209. MMC and CMC Applications
SCPD = Short Circuit Protective Device (Circuit Breaker, Fuses).
MMC = Manual Motor Controller
Reference: Technical Paper AP03402001E.
Note: Line Side Adapters are not required for non-U.S. applications. Most countries outside
of the U.S. classify the MMP as a thermal magnetic circuit breaker.
Accessories
Line Side Adapters
Line Side Adapters are required for use with XTPR MMPs only when used as Type E
Self-Protected Manual Combination Starters or as part of XTFC or XTFR Type F
Combination Motor Controllers. Not required for Group Installation.
Table 210. Line Side Adapters
Combination Connection Kits
Combination Connection Kits include the necessary components to field assemble
a Manual Motor Controller with an MMP (XTPR) and Contactor (XTCE).
Table 211. Combination Connection Kits
Contact Eaton.
XT IEC Manual & Combination Motor Controllers
Line Side Adapter (LSA)
Not required
Manual Motor Controller
XTSC / XTSR
Group Installation
Using the in-panel Main
SCPD
and an MMC
without a factory
assembled LSA.
UL 508 Type F Combination Motor Controller
Only Upstream Feeder SCPD
required with factory
assembled LSA; no dedicated in-panel Main SCPD
for CMC.
Line Side Adapter (LSA)
Required — Factory
Assembled
Combination Motor Controller
XTFC / XTFR
Description Catalog
Number
Price
For use with Frame B MMPs (up to 32A) XTPAXLSA
For use with Frame D MMPs (up to 40A) XTPAXLSAD
Description Catalog
Number
Price
Non-reversing
Includes: Mechanical & Electrical Connection Element
for XTPR…B... (MMP) and XTCE…B… (Contactor).
XTPAXTPCB
Includes: Mechanical & Electrical Connection Element
for XTPR…B... (MMP) and XTCE…C… (Contactor) and
DIN Rail Adapter Plate.
XTPAXTPCC
Includes: Mechanical & Electrical Connection Element
for XTPR…D... (MMP) and XTCE…D… (Contactor) and
DIN Rail Adapter Plate.
XTPAXTPCD
Reversing
Includes: Mechanical & Electrical Connection Element
for XTPR…B... (MMP) and (2) XTCR…B… (Contactors)
XTPAXTPCRB
Includes: Mechanical & Electrical Connection Element
for XTPR…B... (MMP) and (2) XTCR…C… (Contactors)
and DIN Rail Adapter Plate.
XTPAXTPCRC
Includes: Mechanical & Electrical Connection Element
for XTPR…D... (MMP) and (2) XTCR…D… (Contactors)
and DIN Rail Adapter Plate.
XTPAXTPCRD
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . MC7