Technical data

June 2005
144
For more information visit: www.EatonElectrical.ca CAT.02.02.S.K.CD
XT IEC Power Control
Manual Motor Protectors
Technical Data and Specifications
Table 203. Undervoltage Release — Technical Data and Specifications
Table 204. Current Limiter
Table 205. Shunt Release — Technical Data and Specifications
Description XTPAXUVR…
Cross-sections
Solid or flexible conductor with ferrule (mm
2
)1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
Solid or stranded (AWG) 1 x (18 – 14)
2 x (18 – 14)
Main Contacts
Rated operational voltage, U
e
(V AC) 42 – 480
Rated operational voltage, U
e
(V DC) 24 – 250
Pick-up voltage, x U
s
0.85 – 1.1
Drop-out voltage, x U
s
0.7 – 0.35
Power Consumption
Pick-up AC (VA) 5
Sealing AC (VA) 3
Description XTPAXCL
Rated Impulse withstand Voltage (U
imp
), V AC 6000
Overvoltage Category/ Pollution Degree III/3
Rated operational voltage, U
e
(V AC) 690
Rated interrupted current = Rated operational current
(l
u
= l
e
) in amperes
63
Description XTPAXSR __
Cross-sections
Solid or flexible conductor with ferrule (mm
2
)1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
Solid or stranded (AWG) 1 x (18 – 14)
2 x (18 – 14)
Main Contacts
Rated operational voltage, U
e
(V AC) 42 – 480
Rated operational voltage, U
e
(V DC) 24 – 250
AC Operating Range, x U
s
0.7 – 1.1
DC Operating Range, x U
s
(intermittent operation 5s) 0.7 – 1.1
Power Consumption
Pick-up AC (VA) 5
Sealing AC (VA) 3
Pick-up DC (VA) 3
Sealing DC (VA) 3