Technical data

June 2005
142
For more information visit: www.EatonElectrical.ca CAT.02.02.S.K.CD
XT IEC Power Control
Manual Motor Protectors
Technical Data and Specifications
Technical Data and Specifications
Table 201. XT Manual Motor Protectors — Technical Data and Specifications
XTPBP16B –
XTPB016B
XTPRP16B –
XTPR032B
XTPR016D –
XTPR063D
XTPMP16B –
XTPM032B
XTPTP16B –
XTPT025B
General
Standards IEC/EN 60947, VDE 0660, UL 508, CSA C 22.2 No. 14
Climatic proofing
Ambient temperature, °C
Storage
Open
Enclosed
-25 / 80
-25 / 55
-25 / 40
-25 / 80
-25 / 55
-25 / 40
-25 / 70
-25 / 55
-25 / 40
-25 / 80
-25 / 55
-25 / 40
-25 / 80
-25 / 55
-25 / 40
Temperature compensation
to IEC/EN 60947, VDE 0660, °C
Operating range, °C
-5 / 40
-25 / 55
-5 / 40
-25 / 55
-5 / 40
-25 / 55
-5 / 40
-25 / 55
-5 / 40
-25 / 55
Temperature compensation residual
error for T > 20°C, %/K
<
0.25 < 0.25 < 0.25 < 0.25 < 0.25
Mounting position
Direction of incoming supply As required As required As required As required As required
Degree of protection
Device
Terminals
IP20
IP00
IP20
IP00
IP20
IP00
IP20
IP00
IP20
IP00
Protection against direct contact Finger- and back-of-hand proof
Shock resistance half-sinusoidal shock
10 mS to IEC 60068-2-27 (g)
25 25 15 25 25
Altitude (m) max. 2000 max. 2000 max. 2000 max. 2000 max. 2000
Terminal capacity
Solid (mm
2
)
Flexible with ferrule to DIN 46228, (mm
2
)
Solid or stranded (AWG)
1 x (1 – 6)
2 x (1 – 6)
1 x (1 – 6)
2 x (1 – 6)
18 – 10
1 x (1 – 6)
2 x (1 – 6)
1 x (1 – 6)
2 x (1 – 6)
18 – 10
1 x (1 – 50)
2 x (1 – 35)
1 x (1 – 35)
2 x (1 – 35)
14 – 2
1 x (1 – 6)
2 x (1 – 6)
1 x (1 – 6)
2 x (1 – 6)
18 – 10
1 x (1 – 6)
2 x (1 – 6)
1 x (1 – 6)
2 x (1 – 6)
18 – 10
Terminal screw tightening torque
Main cable, Nm
Main cable, lb-in
Control circuit cable, Nm
Control circuit cable, lb-in
1.7
15.0
1
8.9
1.7
15.0
1
8.9
3
26.6
1
8.9
1.7
15.0
1
8.9
1.7
15.0
1
8.9
Main contacts
Rated impulse withstand voltage (U
imp
), V AC 6000 6000 6000 6000 6000
Overvoltage category / pollution degree III / 3 III / 3 III / 3 III / 3 III / 3
Rated operational voltage (U
e
), V AC 690 690 690 690 690
Rated uninterrupted current = rated operational
current (I
u
= I
e
) in amperes
16 or current setting
of the overcurrent
release
32 or current setting
of the overcurrent
release
63 or current setting
of the overcurrent
release
32 or current setting
of the overcurrent
release
25 or current setting
of the overcurrent
release
Rated frequency, Hz 40 – 60 40 – 60 40 – 60 40 – 60 40 – 60
Current heat loss (3-pole at operating
temperature), W
662266
Lifespan, mechanical (ops) 50,000 100,000 30,000 100,000 100,000
Lifespan, electrical (AC-3 at 400 V) (ops) 50,000 100,000 30,000 100,000 100,000
Maximum operating frequency, operations/hr 25 40 40 40 40
90° 90°
90°
90° 90°
90° 90°
90°