Technical data
Table Of Contents

June 2005
124
For more information visit: www.EatonElectrical.ca CAT.02.02.S.K.CD
XT IEC Power Control
Manual Motor Protectors
Product Family Overview
Features
■ ON/OFF Rotary Handle with Lockout
Provision
■ Visible Trip Indication
■ Class 10 Overload Protection
■ Phase Loss Sensitivity
■ Ambient Temperature Compensation
to IEC/EN 60947, VDE 0660
■ Fixed Short Circuit Trip — 14 times
maximum setting of overload FLA
dial
■ Type 2 Coordination per IEC 947
■ Identification Markers Standard on
Starter Faceplate
■ Motor Applications from 0.1A to 63A
■ Built-in heater and magnetic trip
elements to protect the motor
■ Adjustment dial for setting motor
FLA
■ DIN Rail Mount
■ Terminal Types Available:
❑ Screw terminals
❑ Screw (line) and Spring Cage
(load) terminals
❑ Spring Cage terminals
■ Accessories include:
❑ Front and Side Auxiliary Contacts
❑ Trip Indicating Contacts
❑ Tamperproof Cover for OLR Dial
❑ Undervoltage Release
❑ Shunt Trip
❑ Thru-the-Door Operators
❑ Enclosures
❑
3-Phase Line Side Connecting Links
Figure 74. Line Side Adapters — When to Use Them
Note: Line Side Adapters are not required for non-US applications. Most countries outside of
the US classify the MMP as a thermal magnetic circuit breaker.
Standards and Certifications
■ UL Listed
■ UL 508 Group Motor and Type E
Compliant
■ IEC/EN 60947
■ CSA File LR12530, Class 3211-05
■ DIN VDE 0660 Part 100, Part 101 and
Part 102
Types (Configurations)
■ Motor Protective Device with
Thermal and Magnetic Trip
❑
XTPB Pushbutton Actuated Manual
Motor Protector up to 25A
❑ XTPR Rotary Actuated Manual
Motor Protector up to 63A
■ For the Protection of Transformers
with a high inrush current:
❑ XTPT Manual Transformer
Protector up to 25A
■ Motor Protective Device without
Overload Function:
❑ XTPM Motor Protective Circuit
Breaker up to 32A — not UL
Approved
Line Side Adapter
Manual Motor Protectors
Self-Protected Manual Combination Starters
Line Side Adapter (LSA)
Not required
Group Installation
Using the in-panel Main SCPD.
UL 508 Type E Self-Protected Manual
Combination Starter
Only Upstream Feeder SCPD required —
no dedicated in-panel Main SCPD for MMP.
Line Side Adapter (LSA)
Required
LSA
XTPAXLSA
LSA
XTPAXLSAD
MMP
XTPR…BC1
MMP
XTPR…DC1