Technical data

June 2005
124
For more information visit: www.EatonElectrical.ca CAT.02.02.S.K.CD
XT IEC Power Control
Manual Motor Protectors
Product Family Overview
Features
ON/OFF Rotary Handle with Lockout
Provision
Visible Trip Indication
Class 10 Overload Protection
Phase Loss Sensitivity
Ambient Temperature Compensation
to IEC/EN 60947, VDE 0660
Fixed Short Circuit Trip — 14 times
maximum setting of overload FLA
dial
Type 2 Coordination per IEC 947
Identification Markers Standard on
Starter Faceplate
Motor Applications from 0.1A to 63A
Built-in heater and magnetic trip
elements to protect the motor
Adjustment dial for setting motor
FLA
DIN Rail Mount
Terminal Types Available:
Screw terminals
Screw (line) and Spring Cage
(load) terminals
Spring Cage terminals
Accessories include:
Front and Side Auxiliary Contacts
Trip Indicating Contacts
Tamperproof Cover for OLR Dial
Undervoltage Release
Shunt Trip
Thru-the-Door Operators
Enclosures
3-Phase Line Side Connecting Links
Figure 74. Line Side Adapters — When to Use Them
Note: Line Side Adapters are not required for non-US applications. Most countries outside of
the US classify the MMP as a thermal magnetic circuit breaker.
Standards and Certifications
UL Listed
UL 508 Group Motor and Type E
Compliant
IEC/EN 60947
CSA File LR12530, Class 3211-05
DIN VDE 0660 Part 100, Part 101 and
Part 102
Types (Configurations)
Motor Protective Device with
Thermal and Magnetic Trip
XTPB Pushbutton Actuated Manual
Motor Protector up to 25A
XTPR Rotary Actuated Manual
Motor Protector up to 63A
For the Protection of Transformers
with a high inrush current:
XTPT Manual Transformer
Protector up to 25A
Motor Protective Device without
Overload Function:
XTPM Motor Protective Circuit
Breaker up to 32A — not UL
Approved
Line Side Adapter
Manual Motor Protectors
Self-Protected Manual Combination Starters
Line Side Adapter (LSA)
Not required
Group Installation
Using the in-panel Main SCPD.
UL 508 Type E Self-Protected Manual
Combination Starter
Only Upstream Feeder SCPD required —
no dedicated in-panel Main SCPD for MMP.
Line Side Adapter (LSA)
Required
LSA
XTPAXLSA
LSA
XTPAXLSAD
MMP
XTPR…BC1
MMP
XTPR…DC1