User manual
Chapter 6 Parameters Setting in GSD file| CME-PD01
Revision October 2006, 2006PDD23000013 6-7
Data Output 4 = 0x2103;
dout_len = 0x0003;
The MODBUS address in Data Output 1~Data Output 4 is continuous, so you can set the d_state to 1,
then CME-PD01 will monitor the address starting from Data Output 1, and monitor 3 words from VFD-
E series Drives one time. When the dout_len is 3, CME-PD01 will ignore the address in Data Output
4. If d_state is set to 0, CME-PD01 will read data from the address in Data Output 1, and read data
from the address in Data Output 2, and so forth.
The parameters settings are shown in the following:
NOTE
Please do not set d_state to 1 when the address in Data Output 1 ~ Data Output 4 is
discontinuous to avoid parameter process error and IO disconnect. The CME-PD01 just checks
the address starting from Data Output 1 to Data Output [dout_len-1], in other words, if the
address in Data Output 1 ~ Data Output 3 is continuous, but the address in Data Output 4 is not,
and dout_len is 0x0003, then the check still can pass.