Revision October 2006, 2006PDD23000013 5-9
in decimal, if set Page Select to 14, then the Basic PNU is 29952-14*2000=1952(0x7A0),
thus, the data sequence are as follows:
Master - > CME-PD01 : 17A0700000000000 read data from 0x7500
CME-PD01 - > Master : 17A0700000000300
Request Response
Word 1 (PKE) 17A0 Word 1 (PKE) 17A0
Word 2 (IND) 7000 Word 2 (IND) 7000
Word 3 (PWE1) 0000 Word 3 (PWE1) 0000
Word 4 (PWE2) 0000 Word 4 (PWE2) 0300
If the data that CME-PD01 returns is 0x0300, it indicates that Scan port is disconnected.
Please refer to Section 7.2 for details.
Example 5: Access error
When failing to read/write parameters by using PKW, an error message will be shown from
the CME-PD01. Suppose that the data sequence master sent is 202D 8000 0000 0002. If
this address (0x07FD) cannot be found by the VFD-E, it will respond the data sequence
702D 8000 0000 0000, request ID is 7 which means cannot process request (with error
number), and error number is 0 (Illegal Parameter Number).
Request Response
Word 1 (PKE) 202D Word 1 (PKE) 702D
Word 2 (IND) 8000 Word 2 (IND) 8000
Word 3 (PWE1) 0000 Word 3 (PWE1) 0000
Word 4 (PWE2) 0002 Word 4 (PWE2) 0000
5.4 CME-PD01 Response Time
The response (refresh) time via PROFIBUS connection can be divided in 3 parts: