User manual
Chapter 4 Installation Information| CME-PD01
4-2 Revision October 2006, 2006PDD23000013
Power Supply
The power of CME-PD01 is supplied from VFD-E series Drive. The VFD-E firmware
version should be V2.02 and above. No external power needed. The +15VDC power is
applied to CME-PD01 directly via a specific 6-PIN communication cable (This 6-PIN
cable is packed together with CME-PD01).
CME-PD01 is energized while the power is applied to the VFD-E series, then the SP
LED will be steady green.
4.2 Pin Assignment of PROFIBUS-DP Interface (DB9)
Use PROFIBUS-DP interface (DB9) of CME-PD01 connecting CME-PD01 to PROFIBUS DP
system. The terminals are short-circuit-proof and isolated.
1
5
6
9
Pin Designation Description
1 -
Not assigned
2 -
Not assigned
3 Rxd/TxD-P
Receive/send data P (B)
4 - Not assigned
5 DGND
Data reference potential (C)
6 VP
Supply voltage positive
7 -
Not assigned
8 RxD/TxD-N
Receive/send data N (A)
9 -
Not assigned