Specifications
PROFIBUS DP Slave Communicaion Module RTU-PD01
DVP-PLC Operation Manual
7
5 Establishing PROFIBUS DP Network by RTU-PD01
The right-side interface on RTU-PD01 is connectable to DVP-Slim series special I/O modules and
digital I/O modules. The RS-485 port is connectable to standard Modbus devices. See the figure below
for the connection of Slim series I/O modules and Modbus devices and into the PROFIBUS DP
network.
6 Transmission Distance and Baud Rate
The baud rate range for PROFIBUS DP is 9.6kbps ~ 12Mbps, and the length of transmission cable
varies upon the transmission speed. The transmission distance ranges from 100m to 1,200m. See the
table below for the baud rates RTU-PD01 supports and their corresponding communication distance.
Baud rate (bps) 9.6k 19.2k 93.75k 187.5k 500k 1.5M 3M 6M 12M
Distance (m) 1,200
1,200 1,200 1,000 400 200 100 100 100