MOTORSAVER™ THREE-PHASE VOLTAGE MONITOR
455 SERIES
Supply Watts 6W maximum
Frequency 50*/60 Hz
Contact Rating SPDT 480 VA @ 240 VAC pilot duty
10A general purpose SPDT high
voltage relay (-480R) 470 VA @
600 VAC pilot duty
Transient Protection IEC 1000-4-5; 1995 ± 6K1
Line Voltage Monitored
455 190 - 480 VAC
455 - 480R 380 - 480 VAC
455 - 575 475 - 600 VAC
Low Voltage Trip 90% of setpoint (±1%)
Low Voltage Reset 93% of setpoint (±1%)
Reset Delay Time
after Fault Manual or 2-300 seconds
Reset Delay Time after
Power Loss Manual or 2-300 seconds
Trip Delay Time
High Voltage 2-30 seconds, adjustable
Trip Delay Time
Low Voltage 2-30 seconds, adjustable
Trip Delay Time
Phase Fault 0.5 seconds
Trip Delay
Time Unbalance 2-30 seconds, adjustable
Voltage Unbalance
Reset Trip setting minus 1%
Voltage Unbalance Trip 2% to 8%, adjustable
Dimensions 2.9"H x 5.25"W x 2.9"D
(7.4 x 13.3 x 7.4 cm)
Weight 0.88 lb (0.396 kg)
Approvals UL and cUL listed, #E68520, CS1,
C1
Warranty 5 years
DESCRIPTION
The Model 455 three-phase voltage monitor combines load
and line-side monitoring to alert the user of contact failure or
impending contact failure. The line-side monitoring will protect
the motor from damaging line-side conditions prior to the motor
starting. With the Model 455, your motor is fully protected at all
times. The motor will not start if a power problem is present.
The monitor is equipped with an infrared LED to communicate
with the handheld diagnostic tool, the Informer-MS, to display
MotorSaver
®
data to assist in monitoring and troubleshooting the
system. Motor run hours, displayed by the Informer-MS can now
be reset on the Model 455.
INPUT
POWER
L1
M1 M2 M3
L2 L3
OL
OL
OL
B
A
C
MAGNETIC
CONTACTOR
MOTOR
MS455
THERMOSTAT
OPTIONAL
CONTROL
POWER
24 - 240 VAC
TM
M
MAG.
COIL
HAND
STOP
OFF
AUTO
PILOT
START
OL
WIRING
MODEL DESCRIPTION
455 Three-phase voltage monitor, 190-480 VAC
455-480R Three-phase voltage monitor, 380-480 VAC
455-575 Three-phase voltage monitor, 575-600 VAC
INFORMER-MS Hand held diagnostic/trouble shooting tool
SPECIFICATIONS
FEATURES
• The 455's universal range from 190-480VAC 50/60 Hz provides
the versatility needed to handle global applications.
• Four adjustment pots provide versatility for a variety of
applications.
• Load and line-side monitoring provides contactor protection.
• Diagnostic LEDs indicate trip status and provide simple
troubleshooting.
• Microcontroller-based circuitry for better accuracy and higher
reliability.
L1 L2 L3
190-480 VAC, 3Ø, 50/60 HZ
MODEL 455
OVER
VOLT.
PHASING
FAULT
UNDER
VOLT.
PILOT DUTY RATING
480 VA AT 240 VAC
RUN
VOLT. ADJ.
(VAC)
208
416
220
440
200
400
230
460
190
380
240
480
UNBALANCE
TRIP (NEMA %)
8
2
M1 M2 M3
SymCom. Inc.
300
100
2
MAN
RESTART
(SEC)
30
2
15
TRIP
DELAY
(SEC)
IR
LINK
IND. CONT. EQ.
LISTED
784X
4.030 (102.36)
5.250 (133.35)
4.500 (114.30)
Ø 0.375
(9.53)
2.9
(73.66)
0.150 (3.81)
2.163
(54.94)
2.913
(73.99)
Model 455
* 50 Hz will increase all delay times by 20%.
• Single-phase conditions are detected regardless of
regenerated voltages.
• Transient protection meets IEEE and IEC standards and
permits operation under tough conditions.