Description Default value
Operation mode
Select the roles and operating agreement for present network and serial ports via
following options:
1. MODBUS ASCII Slave: The network port for DVW device operates in MODBUS
TCP Server mode, the RS-485 serial port operates in MODBUS ASCII master
mode.
2. MODBUS RTU Slave: The network port for DVW device operates in MODBUS
TCP Server mode, the RS-485 serial port operates in MODBUS RTU master
mode.
3. MODBUS ASCII Master: The network port for DVW device operates in
MODBUS TCP client mode, the RS-485 serial port operates in MODBUS ASCII
slave mode.
4. MODBUS RTU Master: The network port for DVW device operates in MODBUS
TCP client mode, the RS-485 serial port operates in MODBUS RTU slave mode.
Close
Configuring
RS485
Data bit
Displays serial port data bit; the value is fixed to 7 in ASCII protocol,
the value is fixed to 8 in RTU protocol.
N/A
Parity bit
Configuring parity for serial port. Optional values include “none”, “odd”
or “even”.
None
Stop bit