Chapter 1 Product introduction Table of Contents 1.1 Overview .................................................................................................... 1-4 1.1.1 High performance wireless technology ....................................................... 1-4 1.1.2 Good reliability and design optimization ..................................................... 1-5 1.1.3 Robust design for industrial hardware........................................................ 1-5 1.1.
_1 De lta In dus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l About this Manual This manual contains information about DVW-W01I2-E1 series. When using Delta DVW series product in China, please refer to Delta official website with model name DVW-W01I2-E1 or contact our nearest branch offices or distributors for further information. FCC Interference Statement This equipment has been tested and found to comply with the limits for a class A digital device, pursuant to part 15 of the FCC Rules.
Ch ap te r 1 Prod uc t in tr od uc tion claim or in connection with the use of or access to the Software or Services. Warning 此设备应安装在限制进出的场所。限制进出场所指仅能透过特殊工具、锁和钥匙或 1_ 其他安全手段才能进出的场所。 This equipment should be installed in a place where access is restricted. Restricted places are places that can only be accessed through special tools, locks and keys or other security means.
_1 De lta In dus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 1.1 Overview Delta’s industrial wireless DVW-W01I2-E1 series features Ethernet port, RS-232 and RS-485, supports standard MODBUS protocol for executing and controlling data transmission with operating devices.
Ch ap te r 1 Prod uc t in tr od uc tion 1.1.2 Good reliability and design optimization Redundant dual DC power input One set of digital input (DI) One set of alarm output (DO) 1.1.3 1_ Robust design for industrial hardware Operating temperature: -10~60℃ Storage temperature: -40~85℃ Humidity: 5%~95% (non-condensing) Metal case: IPX0 1.1.4 Product profile and dimensions 6 31 110 13.5 3.4 8.
_1 De lta In dus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l No 1 2 3 4 5 6 7 8 Description LED indicator Antenna socket Signal strength Ethernet port RS-485 port RS-232 port Power terminal Reset button 1.
Ch ap te r 1 Prod uc t in tr od uc tion 1_ 1.3.
_1 De lta In dus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 1.3.3 Wiring the redundant power input The DVW-W01I2-E1 is equipped with one to two sets of DC input (PWR1 / PWR2). Both sets of DC input can be connected to a wide range of power sources (12 to 48VDC). When one power source fails, the other source can work as a backup to ensure that the machine operates normally.
Ch ap te r 1 Prod uc t in tr od uc tion 1_ 1.3.5 Wiring the digital input The DVW-W01I2-E1 is equipped with one to two sets of digital input. When input voltage is between 0 to 5V, the state of DI is OFF; input voltage between 11 to 30V, the state of DI is ON. The maximum input current is 6mA.
De lta In dus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 1.3.6 Pin definition RS-232 & RS485 Pin no. _1 RS-232 Pin no.
Ch ap te r 1 Prod uc t in tr od uc tion 1.3.7 Wiring RS-232 RS-485 R S-232 R S-232 RX D TX SG RT S C TS TXD GN D R TS C TS 5 9 4 8 3 7 2 6 1 RX P in Pin 6 1 2 RX D 7 RT S 3 T X D 8 CT S 9 4 5 G ND Master node Slave node Slave node D+ D- SG D+ D- S G SG D+ D- Terminal resistor (120 ohm) Terminal resistor (120 ohm) 1.
2 Chapter 2 User Interface Table of Contents Chapter 2 User Interface ..................................................................................................... 2-1 2.1 Configuration ................................................................................................................... 2-2 2.2 Connection and access settings ........................................................................................ 2-2 2.3 General configurations .........................................
_2 De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 2.1 Configuration Before using DVW-W01I02-E1 series, please pay attention to the following item preparation. No Item 1 PC 2 3 Description Contains Windows operating system and web browsers. Power supply Supports 12-48V with output power larger than 2.5W. Cable Includes 5 types of twisted pair as communication cables of DVW-W01I02-E1. 2.2 Connection and access settings 1.
Ch ap te r 2 User In ter fac e 2_ Manually configure the local IP address. Since the default IP address is 192.168.1.5 for router settings, the subnet masks is 255.255.255.0, therefore, the local IP on PC can be set anywhere between 192.168.1.1 to 254 excluding 192.168.1.5 and with no repeating IPs. We setup the IP address as 192.168.1.10, the default gateway is 192.168.1.5, select an available DNS address or configuring to 192.168.1.5.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 3. Open browser (e.g. IE) then type in default IP address 192.168.1.5 and click enter. The following log-in page appears for users to enter the correct username and password (Default setting: admin/password). _2 2.3 General configurations 2.3.1 AP mode setup In AP mode, the access point serves as intermediate point between devices for wired or wireless connection and data transmission. Configuration procedures 1.
Ch ap te r 2 User In ter fac e 2_ 3. From WLAN2.4G listed on the menu, select Operation Mode, choose AP mode and click Apply. 4. Select Basic Configuration and setup SSID name as well as WPA2-PSK for security mode (recommended), then click Apply. 5. For wireless client, search for DVW SSID (SlimWiFi_B4F8) in the AP list and click to complete on-line data transmission via wireless connection.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l _2 2.3.2 Client mode setup When users have two DVW devices, one uses AP mode and the other as client mode, both are combined via wireless connection. However, only LAN connection can be used in client mode but not wireless devices or connections. Configuration procedures 1. Set all IP addresses in the same segment. 2. AP mode: please refer to section 2.3.1. 3.
Ch ap te r 2 User In ter fac e 2_ 4. From WLAN2.4G listed on the menu, select Operation Mode, choose Client mode and click Apply. 5. Select Basic Configuration and click “Site Survey”. 6. Select the configured AP SSID (e.g. SlimWiFi_4456). When SSID cannot be found, please click “Refresh”.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 7. Type in the password for AP setting and click APPly to complete Client and AP connection. _2 8. When connection is complete, select Ping under Maintenance. Then, type in destination IP to test the connection. For successful connection, the AP Ping response time appears.
3 Chapter 3 Function Guide Table of Contents System ....................................................................................................... 3-2 3.1 3.1.1 System configuration................................................................................. 3-2 3.1.2 System CPU status .................................................................................... 3-2 3.2 Basic configuration ..................................................................................... 3-3 3.2.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 3.1 System The main display focuses on DVW-W01I2-E1 series present system information and CPU status. 3.1.1 System configuration Displays information which can be categorized into three parts: System Configuration, Device Info and 802.11 Info. _3 3.1.2 System CPU status Displays system’s present CPU status which includes running time, total power-on time, CPU usage, total RAM and RAM available.
Ch ap te r 3 Fu nc tion G uide 3.2 Basic configuration The basic configuration allows users to perform maintenance and setup for DVW-W01I2-E1 series including system information and network. 3_ 3.2.1 System information The configuration contains user-defined device name, location, description and contact information. Through this setup, users can easily and clearly identify each DVW-W01I2-E1 used on the network.
_3 De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 3.2.2 Network configuration Network configuration allows users to setup IP, IP address, IP subnet mask, gateway IP and primary DNS. There are several IP modes available for network configuration. Users can select modes from DHCP-Client, Static and DHCP-Server.
Ch ap te r 3 Fu nc tion G uide Description Configure IP address and identify DVW-W01I2-E1 series in TCP/IP network. IP subnet mask Set the IP subnet mask of router LAN ports. (Example: 255.0.0.0 is Type A address; 255.255.0.0 is Type B address; 255.255.255.0 is Type C adderss) Gateway IP Connect DVW-W01I2-E1 to WAN IP gateway. Primary DNS Connect DVW-W01I2-E1 to primary DNS in WAN configuration that translates domain names into IP addresses.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l Attention For RS-232 and RS-485, the configured map ID range cannot have repeated regions, because the system forwards the request to serial ports base on the network port of the map ID in the request data. _3 MODBUS ASCII / RTU Master In this mode, the DVW series serve as MODBUS ASCII/RTU Slave.
Ch ap te r 3 Fu nc tion G uide 3_ 3-7
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l _3 Description Operation mode Select the roles and operating agreement for present network and serial ports via following options: 1. MODBUS ASCII Slave: The network port for DVW device operates in MODBUS TCP Server mode, the RS-485 serial port operates in MODBUS ASCII master mode. 2. MODBUS RTU Slave: The network port for DVW device operates in MODBUS TCP Server mode, the RS-485 serial port operates in MODBUS RTU master mode. 3.
Ch ap te r 3 Fu nc tion G uide Description Configuring stop bit for serial port. Optional values include 1 or 2. Others Slave mode Master modeForward table 3.3.1.2 Baud rate Configuring baud rate for serial port. Optional values include 2400, 4800, 9600, 19200, 38400, 57600, 115200. Station ID Displays the station ID of the device. The station ID of RS-485 is 247. TCP keepalive time Configure DVW device in idle TCP connection to setup TCP keep-alive time.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l For instance, RS-232 serial port slave ID setting range is 1-20, map ID setting range 1-20; while RS-485 serial port slave ID setting range is 1-20 and map ID setting range is 21-40.
Ch ap te r 3 Fu nc tion G uide 3_ Description Operation mode Select the roles and operating agreement for present network and serial ports via following options: 1. MODBUS ASCII Slave: The network port for DVW device operates in MODBUS TCP Server mode, the RS-485 serial port operates in MODBUS ASCII master mode.
_3 De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l Description 2. MODBUS RTU Slave: The network port for DVW device operates in MODBUS TCP Server mode, the RS-485 serial port operates in MODBUS RTU master mode. 3. MODBUS ASCII Master: The network port for DVW device operates in MODBUS TCP client mode, the RS-485 serial port operates in MODBUS ASCII slave mode. 4.
Ch ap te r 3 Fu nc tion G uide 3.3.2.1 RS-485 In this mode, the DVW series is used as client’s serial server of communication via TCP/UDP protocol which can transmit RS-485 data to the serial server.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l _3 Description Operation mode Select the current operating serial port default to “Close”, other options include: 1. TCP mode: serve as client’s serial server of communication via TCP protocol. 2. UDP mode: serve as client’s serial server of communication via UDP protocol. Baud rate Set baud rates for serial ports. Optional values include 2400, 4800, 9600, 19200, 38400, 57600, 115200. Data bit Serial Set data bits for serial ports.
Ch ap te r 3 Fu nc tion G uide UDP mode 3.3.2.2 Description 1~99: When idle time reaches setting value, TCP connection is closed. Destination IP and port Set connected serial server IP range and port, the IPand port cannot have the same configuration. Max. 4 serial servers for simultaneous connection. Max. payload length Set the waiting length of cumulative data for data packet transmission, the range is 0 to 1024 byte; set 0 for immediate data transmission.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l _3 3-16
Ch ap te r 3 Fu nc tion G uide 3_ Description Operation mode Select the present operating serial port default to “Close”, other options include: 1. TCP mode: serve as client’s serial server of communication via TCP protocol. 2. UDP mode: serve as client’s serial server of communication via UDP protocol. Baud rate Set baud rates for serial ports. Selected values include 2400, 4800, 9600, 19200, 38400, 57600, 115200. Data bit Serial Set data bits for serial ports. Optional values include 7 or 8.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l TCP mode _3 UDP mode 3.3.3 Description Flow Control Set types of flow control. Optional values include “XON/XOFF”, “RTS/CTS”. TCP keepalive time Configure idle time of TCP to auto-close TCP connection. Optional values from 0 to 99 minutes. 0: TCP connection will not be closed due to idle (always open) 1~99: When idle time reaches setting value, TCP connection is closed.
Ch ap te r 3 Fu nc tion G uide 3_ Description Operation mode Select present operating serial port mode from the following options: 1. TCP server: as TCP server, create connection once receive client host request then client host and DVW device can start data transmission. 2. Close: close transparent server function. TCP port Set the port for TCP Server monitoring data packet. Baud rate Set baud rates for serial ports. Optional values include 2400, 4800, 9600, 19200, 38400, 57600, 115200.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l _3 Description Operation mode Select present operating serial port mode from the following options: 1. TCP server: as TCP server, create connection once receive client host request then client host and DVW device can start data transmission. 2. Close: close transparent server function. TCP port Set the port for TCP Server monitoring data packet. Baud rate Set baud rates for serial ports.
Ch ap te r 3 Fu nc tion G uide 3.3.4 MODBUS cache table Since the transmission speed of Ethernet interface is faster than that of serial ports, therefore, when Ethernet devices send requests to serial devices, more time is required for waiting serial port data. MODBUS cache table provides PLCs with relevant configuration information (e.g. station ID, MODBUS IP). The DVW device can send request to receive serial port device data based on prior MODBUS cache table.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l Explanation Add Add a configuration message (up to 100 messages). Edit Edit selected configuration messages. Delete Delete assigned configuration messages. Online When clicked, real-time values gathered for relevant addresses are shown on the right section of the page. _3 Word device Item Station address MODBUS (Hex) MODBUS (Dec) Present value Format Explanation The device station ID.
Ch ap te r 3 Fu nc tion G uide Explanation Set format to Hex, Dec, Bin (hexadecimal, decimal, binary). When add or edit coil device types, format is not required. Online Set or not to set data display on MODBUS monitoring table. 3.3.4.2 Default value Hex Not checked RS-232 cache table On the left part of the cache table page displays information regarding configuration; click Online and data read based on configuration messages are shown on the right.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l Explanation Displays the available data size for monitoing. Timeout calibration Calibrate the response timeout. When users click Detect, the DVW device will use the MODBUS cache table for communication. Add Add a configuration message (up to 100 messages). Edit Edit selected configuration messages. Delete Delete assigned configuration messages.
Ch ap te r 3 Fu nc tion G uide Explanation Starting from MODBUS address and connecting to monitored data size. Format Set format to Hex, Dec, Bin (hexadecimal, decimal, binary). When add or edit coil device types, format is not required. Online Set or not to set data display on MODBUS monitoring table. Default value None Hex Not checked 3.4 WLAN management - 2.4G The WLAN management focuses on configuring 2.4G WIFI operation mode and its corresponding parameters.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 3.4.2.1 Basic configuration The setting corresponds to operation mode. Different operation mode will have different basic configurations. AP mode: In AP mode, users can add or edit WLAN basic configurations. For example, RF type, channel, SSID, SSID broadcast and security mode. Click Apply once configurations are completed.
Ch ap te r 3 Fu nc tion G uide Description WMM After selecting this option, multimedia data is given priority during data transmission. Client isolation After selecting this option, clients connected to this AP cannot access each other. Security mode Set AP operation security mode from the following options: None WPA2-PSK[AES] WPA-PSK[TKIP]+ WPA2-PSK[AES] For more security mode information, refer to section 3.4.2.2.
_3 De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l Description EXTAP Enabled: When EXTAP is enabled, client compatibility increases along with more compatible AP. Disabled: When EXTAP is disabled, recommend using the AP of DVW-W01I2-E1 for enhanced connection. Client mode Disabled: Operation under normal WiFi client mode. Roaming: client support fast roaming protocol of personal level.
Ch ap te r 3 Fu nc tion G uide Description channel.Setting range: 10~200ms. Scan period Default value Set the AP interval period for DVW scan. Setting range: 1000~300000ms。 Scan threshold Set the AP threshold once DVW is triggered for scanning, but only when the AP’s transmission power connected to the present DVW is lower than the threshold value, the DVW will scan the available AP based on the scan period. Setting range: -95~0 dBm.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l Description Password phrase requires 8 to 63 ASCII characters or 64 hexadecimal digit. 3.4.2.3 Default value None Advanced configuration The configuration provides users to execute advanced parameter settings based on different on-site wireless environment. Description Transmission power Set the transmission power. The transmission power gets stronger as setting value becomes higher and the influence range widens.
Ch ap te r 3 Fu nc tion G uide Description RF To enable or disable wireless function. Operation mode Set wireless operation mode: AP mode: used as an intermediate point for wired and wireless devices connection, data transmission and more. Client mode: DVW-W02W2-E2 operating in client mode can perform wireless data transmission via AP. Region Show the country or region for the device (display only, can’t revise by user) Default value Enabled AP U.S Attention 2.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l Description Operation mode Display present operation mode RF type Select from the following types: AC/N Mixed: only supports mixed mode IEEE 802.11ac/n A/N Mixed: supports mixed mode IEEE 802.11a/n N Only: only supports 5GHz IEEE 802.11n standard A: only supports 5GHz IEEE 802.
Ch ap te r 3 Fu nc tion G uide 3_ Description EXTAP Enabled: When EXTAP is enabled, client compatibility increases along with more compatible AP. Disabled: When EXTAP is disabled, recommend using the AP of DVW-W01I2-E1 for enhanced connection. Client mode Disabled: Operation under normal WiFi client mode.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l Description Client Mode To enable or not enable fast roaming function. Scan channel Set DVW scan strategy, the system offers two options.
Ch ap te r 3 Fu nc tion G uide Description Roaming threshold Set DVW roaming threshold which is a condition for DVW to execute switch action. When the present AP’s transmission power in connection with DVW is lower than the setting value, the DVW can switch to new AP. Setting range: -95~0 dBm. Roaming detect period Set DVW to detect whether the interval period of the two roaming conditions are satisfied; when both conditions are satisfied, the DVW can execute switching. Setting range: 50~300000ms. 3.5.2.
_3 De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 3.7 Maintenance 3.7.1 Session timeout Users can set session timeout but when the setting time is exceeded, it will auto log off the system and a message regarding the action is presented to users. We recommend configuring this function for enhanced system security. Description Session timeout Set the time for session timeout. Timeout setting range is 0 to 60 min. Set to 0 and session timeout will never occur. 3.7.
Ch ap te r 3 Fu nc tion G uide Description Old password The current admin. password New password Set new admin. password Repeat new password Repeat the new password 3.7.3 Default value System log backup The function allows documents derived from the logs to be stored in PCs or storage devices. 3.7.
_3 De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 3.7.5 Serial log From selecting a serial, users can determine the assigned log level and serial logs. The image above shows the system can derive all log level as “Error” from RS232 serial logger. Users can click Backup button and download the logs in PCs. 3.7.6 Ping Ping function can help admin to analyze network status. Type in the IP address to search for connection status. 3.7.
Ch ap te r 3 Fu nc tion G uide 3.7.8 Firmware upgrade DVW-W01I2-E1 releases new upgraded firmware regularly to enhance product performance and include more functions. We strongly recommend users to do regular checkup and proceed firmware upgrade for your DVW-W01I2-E1 device. Please download the latest firmware document for our website. 3.7.9 Configuration Import & Export The “Backup” button allows the documents derived from current configuration messages to store in your PCs or storage devices.
De lta Indus tr ia l W ire less D VW-W0 1 I2- E1 Ser ies Us er Man ua l 3.7.11 Log off Users can click Log off to exist the configuration page. When configuration and operating on the DVW-W01I2-E1 device is complete, we recommend to log off from your current account for security consideration. When Log off is clicked, the log-in page appears.