Specifications
- 10 -
INA INB
Content Explanation CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
Read/write output 1 value Unit: 0.1 %
H1070
(H110E)
H1071
(H120E)
H1072
(H130E)
H1073
(H140E)
H1074
(H150E)
H1075
(H160E)
H1076
(H170E)
H1077
(H180E)
Read/write output 2 value Unit: 0.1 %
H1078
(H110F)
H1079
(H120F)
H107A
(H130F)
H107B
(H140F)
H107C
(H150F)
H107D
(H160F)
H107E
(H170F)
H107F
(H180F)
Upper limit for alarm output
Alarm enabled when
temperature exceeds
upper limit
H1080
(H1110)
H1081
(1210)
H1082
(H1310)
H1083
(H1410)
H1084
(H1510)
H1085
(H1610)
H1086
(H1710)
H1087
(H1810)
Lower limit for alarm output
Alarm enabled when
temperature falls below
lower limit
H1088
(H1111)
H1089
(H1211)
H108A
(H1311)
H108B
(H1411)
H108C
(H1511)
H108D
(H1611)
H108E
(H1711)
H108F
(H1811)
Tuning for upper limit of
analog output
Current (4 ~ 20mA) or
voltage output tuning
H1090
(H1112)
H1091
(H1212)
H1092
(H1312)
H1093
(H1412)
H1094
(H1512)
H1095
(H1612)
H1096
(H1712)
H1097
(H1812)
Tuning for lower limit of
analog output
Current (4 ~ 20mA) or
voltage output tuning
H1098
(H1113)
H1099
(H1213)
H109A
(H1313)
H109B
(H1413)
H109C
(H1513)
H109D
(H1613)
H109E
(H1713)
H109F
(H1813)
Input sensor type See “Input” section
H10A0
(H1114)
H10A1
(H1214)
H10A2
(H1314)
H10A3
(H1414)
H10A4
(H1514)
H10A5
(H1614)
H10A6
(H1714)
H10A7
(H1814)
Output function for output 1
0: heating
1: cooling
2: proportional output
H10A8
(H1115)
H10A9
(H1215)
H10AA
(H1315)
H10AB
(H1415)
H10AC
(H1515)
H10AD
(H1615)
H10AE
(H1715)
H10AF
(H1815)
Output function for output 2
0: heating (default)
1: cooling
2: alarm
H10B0
(H1116)
H10B1
(H1216)
H10B2
(H1316)
H10B3
(H1416)
H10B4
(H1516)
H10B5
(H1616)
H10B6
(H1716)
H10B7
(H1816)
Control method
0: PID
1: ON-OFF
2: manual
3: PID programmable
H10B8
(H1117)
H10B9
(H1217)
H10BA
(H1317)
H10BB
(H1417)
H10BC
(H1517)
H10BD
(H1617)
H10BE
(H1717)
H10BF
(H1817)
Alarm 1 output mode
See “Alarm Output”
section
H10C0
(H1118)
H10C1
(H1218)
H10C2
(H1318)
H10C3
(H1418)
H10C4
(H1518)
H10C5
(H1618)
H10C6
(H1718)
H10C7
(H1818)
Alarm 2 output mode
See “Alarm Output”
section
H10C4
(H1518)
H10C5
(H1618)
H10C6
(H1718)
H10C7
(H1818)
Heating/cooling cycle for
output 1
1 ~ 99 seconds
0 = 0.5 second
H10C8
(H1119)
H10C9
(H1219)
H10CA
(H1319)
H10CB
(H1419)
H10CC
(H1519)
H10CD
(H1619)
H10CE
(H1719)
H10CF
(H1819)
Heating/cooling cycle for
output 2
1 ~ 99 seconds
0 = 0.5 second
H10D0
(H111A)
H10D1
(H121A)
H10D2
(H131A)
H10D3
(H141A)
H10D4
(H151A)
H10D5
(H161A)
H10D6
(H171A)
H10D7
(H181A)
Run/Stop the control
0: stop
1: executing
2: program stops
3: program pauses
H10D8
(H111B)
H10D9
(H121B)
H10DA
(H131B)
H10DB
(H141B)
H10DC
(H151B)
H10DD
(H161B)
H10DE
(H171B)
H10DF
(H181B)
Status of PID auto-tuning
0: stop
1: executing
H10E0
(H111C)
H10E1
(H121C)
H10E2
(H131C)
H10E3
(H141C)
H10E4
(H151C)
H10E5
(H161C)
H10E6
(H171C)
H10E7
(H181C)
Positive/negative
proportional output
0: positive
1: negative (slope)
H10E8
(H111D)
H10E9
(H121D)
H10EA
(H131D)
H10EB
(H141D)
H10EC
(H151D)
H10ED
(H161D)
H10EE
(H171D)
H10EF
(H181D)
Other statuses Other statuses
H10F0
Temperature
unit
H10F1
Open special
function
(H1234)
H10F2
Return to
default
(H1357)
H10F3
Reserved
H10F4
Reserved
H10F5
Reserved
H10F6
Reserved
H10F7
Reserved
Communication
specifications
See Table 4
H10F8
Auto ID
setup
H10F9
Reserved
H10FA
Baudrate
H10FB
ASCII = 0
RTU = 1
H10FC
8 bits=0
7 bits=1
H10FD
2 stop=0
1 stop=1
H10FE
Parity
H10FF
Address
1 ~ 247
LED status
b1: Alarm 2; b2: °C;
b3:°F; b4: Alarm 1;
b5: OUT2; b6: OUT1;
b7: AT
H1124 H1224 H1324 H1424 H1524 H1624 H1724 H1824