Instruction Manual
DOP-107H 
High color‧Controllable‧User-friendly 
Delta Electronics Inc, 
No.18, Xinglong Rd., Taoyuan City 
33068, Taiwan 
Instruction Sheet 
(1) General precautions 
Thank you for purchasing this product. This DOP-107H instruction sheet provides information for the DOP-107H series 
HMI. Before using this product, read through this instruction sheet carefully to ensure the correct use of the product. 
Keep this sheet handy for quick reference whenever needed. Before finishing reading this sheet, follow the following 
instructions. 
  Install the product in an indoor environment which is free of vapor, corrosive and inflammable gas. 
  Refer to the wiring diagram when connecting the wires. 
  Ensure this product is correctly grounded. The grounding method must comply with the national standard 
guidelines (refer to NFPA 70: National Electrical Code, 2005 Ed.). 
  Do not change the wiring when power is on. 
  Do not touch the power supply when power is on, or it may cause electric shock. 
  When the HMI displays a low power notification and requires a battery change, contact the local distributor or 
Delta Customer Service Center for the replacement. Do not change the batteries by yourself. 
If you have any inquiry during operation, contact the local distributors or Delta Customer Service Center. The instruction 
sheet may be revised without prior notice. Contact our distributors or download the latest version from the Delta website 
(http://www.deltaww.com). 
(2) Safety precautions 
Pay attention to the following safety precautions during installation, wiring, operation, maintenance, and inspection. 
Installation 
  Comply with the instructions specified in the user manual for installation, or it may cause damage to 
the equipment. 
  Avoid exposing the product to an environment containing vapor, corrosive gas, inflammable gas, or 
other foreign matter, or it may cause product damage, electric shock, fire, or explosion. 
  Do not install the HMI in an environment where the ambient temperature exceeds the specified 
range, or it may cause abnormal operation or product damage.   
  This product has the approval of KC Class A (for commercial devices), which is designed for 
commercial or industrial use, rather than for domestic use. If you have unintentionally purchased or 
sold the HMI products, replace them with products having the approval of KC Class B (for domestic 
use). 
  Do not install the HMI to the machinery that may cause personnel injury, equipment damage, or 
emergency stop. 
Wiring 
  Connect the ground terminals to class-3 ground system. Ground resistance should not exceed 100Ω. 
Improper grounding may cause communication error, electric shock, or fire. 
  Do not connect other wire rods to extend the cable length, or it may cause poor communication or 
malfunction.   
Operation 
  Program the HMI screens with the DOPSoft software. If the HMI is not well-programmed, it may 
cause abnormal operation. To avoid personnel injury or equipment damage during operation, ensure 
the communication error occurring between the HMI and controller or equipment does not cause 
malfunction when programming the HMI screens. 
  Back up the programmed HMI screens and programs to avoid unexpected data loss.   
  Place the HMI on a flat surface or hang it with the hook on its back to prevent it from falling and thus 
crashing.   
  Do not change the wiring when power is on, or it may cause electric shock or personnel injury. 
  Do not touch the panel with sharp objects, or it may make a dent in the panel, resulting abnormal 
operation of the HMI. 
Maintenance and inspection 
  Do not touch the internal parts of the HMI, or it may cause electric shock or product damage. 
  Do not touch the wiring terminals within 10 minutes after turning off the power. The residual voltage 
may cause electric shock. 
Wiring method 
  The voltage applied to the HMI should not exceed the specified range, or it may cause product 
damage, electric shock, or fire.   
  If any cable removal is forced, check the connection again before resuming the operation. 
Communication wiring 
  Ensure the ground circuit is correct to avoid poor communication. 
  To prevent excessive interference from causing abnormal operation of the HMI, place the 
communication cable, all power cables, and the motor power cable in separate conduits. 
(3) Model explanation 
 (1) 
DOP
 (2) 
1
 (3) 
07
 (4) 
HS
 (5) 
4
 (6) 
6
 (7) 
5
 (8) 
ZM
(1) 
Product name 
DOP: Delta Operation Panel (HMI) 
(2) 
Series 
1: 100 series HMI 
(3) 
Panel size 
07: 7.0" 
(4) 
Type 
HE: Ethernet 
HS: standard 
(5) 
Display 
resolution 
4: WVGA 
(6) 
External device 
Code 
MPG 
SD 
15 Keys 
21 Keys 
2 
● 
● 
6 
● 
● 
● 
7 
● 
● 
● 
(7) 
Cable length 
5: 5 m 
A: 10 m 
(8) 
Connector 
ZM / ZD: D-SUB connector 
(4) Description of each part 
  DOP-107HE42x / DOP-107HE46x / DOP-107HS42x / DOP-107HS46x (front view) 
DOP-107HE42xZM / DOP-107HE46xZM (front view) 
DOP-107HE47xZD (front view) 
1 
Power indicator 
4 
Auxiliary keyboard 
2 
Emergency stop switch 
5 
Operation / display area 
3 
MPG 
- 
- 
DOP-107HE42x /DOP-107HE42xZM / DOP-107HE46x / DOP-107HE46xZM / /DOP-107HE47xZD / DOP-107HS42x / 
DOP-107HS46x (rear view) 
1 
3-position operation switch 
2 
Bus 
DOP-107HE42x / DOP-107HE42xZM / DOP-107HE46x / DOP-107HE46xZM / DOP-107HE47xZD / DOP-107HS42x / 
DOP-107HS46x (bottom view) 
1 
USB slave 
2 
SD card 
(5) Installation environment 
Before installation, this product must be kept in the shipping carton. In order to retain the warranty coverage and for 
maintenance, follow the following instructions for storage. While the product is temporarily not in use: 
  Store the product in a dust-free and dry place. 
  Store the product in an ambient temperature of -10°C to +60°C (14°F to 140°F). 
  Store the product in a relative humidity range of 10% to 90% RH (non-condensing). 
  Avoid storing the product in an environment containing corrosive gas and liquids. 
  Properly wrap the product and place it on a shelf or platform. 
  The suitable installation environment should be a location that is free of devices that generate excessive heat, 
water, vapor, dust and oily dust, corrosive and inflammable gas and liquids, airborne dust and metal particles, 
vibration, and electronic interference. 
  This product must be used at an altitude below 2,000 m (6,561.68 feet). 
(6) Wiring 
D-SUB connector 
Pin assignment for DOP-107HE42xZM / DOP-107HE46xZM / DOP-107HE47xZD series (D-SUB) 
25-pin D-SUB 
Function 
1 
LAN RD+ 
2 
LAN RD- 
3 
Reserved 
7 
Emergency stop – NO(A)   
8 
Emergency stop – NO(A) 
9 
Emergency stop – NC(B) 
10 
Emergency stop – NC(B) 
13 
0Vdc input (use SELV power supply, isolated from MAINS by double insulation) 
14 
LAN TD+   
15 
LAN TD- 
18 
external power input of MPG 
20 
output point A of MPG 
21 
output point B of MPG 
22 
3-position operation switch – NO(A) 
23 
3-position operation switch – NO(A) 
25 
24Vdc input (use SELV power supply, isolated from MAINS by double insulation) 