User manual

3. System Installation
3-2 DVP-MC operating manual
Electrical specification for the output point
Item Content
Input channel
number
4 transistors for output (Source)
Channel type High-speed digital output type for the 4 channels
Output terminals Terminal: Q0, Q1, Q2, Q3
Power voltage for
output point
24 VDC-15% ~ +20%
#1
Output delay 2µS Off -> On, 3µS On -> Off
Max switch
frequency
1KHZ
Resistance: 0.5A/1point 2A/ZP
Inductance: 15W30VDC
Max loading
Bulb: 2.5W30VDC
The Shielded cable: 500m
Max cable length
The cable without a shield wire: 300m
#1: UP and ZP must connecte the auxiliary power 24VDC-15%~20%.