User's Manual
Table Of Contents
- Preface
- Table of Contents
- Chapter 1 Introduction
- 1.1 Receiving and Inspection
- 1.2 Appearances
- 1.3 Installation Steps
- 1.4 Storage
- Chapter 2 Installation and Wiring
- Chapter 3 Start Up
- Chapter 4 Digital Keypad Operation
- Chapter 5 Parameters
- Chapter 6 Fault Code Information
- Chapter 7 Troubleshooting
- 7.1 Over Current (OC)
- 7.2 Ground Fault
- 7.3 Over Voltage (OV)
- 7.4 Low Voltage (Lv)
- 7.5 Over Heat (OH)
- 7.6 Overload
- 7.7 Keypad Display is Abnormal
- 7.8 Phase Loss (PHL)
- 7.9 Motor cannot Run
- 7.10 Motor Speed cannot be Changed
- 7.11 Motor Stalls during Acceleration
- 7.12 The Motor does not Run as Expected
- 7.13 Electromagnetic/Induction Noise
- 7.14 Environmental Condition
- 7.15 Affecting Other Machines
- Chapter 8 Maintenance and Inspections
- Appendix A Specifications
- Appendix B Accessories
- Appendix C How to Select the Right AC Motor Drive
- Appendix D CE

Chapter 5 Parameters|VFD-S Series
5-2 Revision August 2006, SE08, SW V2.61
5.1 Summary of Parameter Settings
: The parameter can be set during operation.
Group 0 User Parameters
Pr. Explanation Settings
Factory
Setting
NOTE
0-00 Identity Code of the AC Motor Drive Read-only d #
0-01 Rated Current Display of the AC
Motor Drive
Read-only d##.#
0-02 Parameter Reset d09: All parameters are reset to
factory settings (50Hz,
220V/380V)
d10: All parameters are reset to
factory settings (60Hz,
220V/440V)
d0
0-03 Start-up Display Selection
d0: Display the frequency command
value (LED F)
d1: Display the actual output
frequency (LED H)
d2: Multifunction display, see Pr.00-
04
d3: Display output current (LED A)
d4: Display forward/reverse
command (Frd/rEv)
d0
0-04 Content of Multi-Function Display
d0: Display User-Defined Unit (u)
d1: Display Counter Value (C)
d2: Display Process Operation (1.tt)
d3: Display DC-BUS Voltage (
u
)
d4: Display output voltage (E)
d5: Display frequency commands of
PID (P)
d6: Display analog feedback signal
value (b) (%)
d0
0-05 User-Defined Coefficient K d0.1 to d160 d1.0
0-06 Software Version Read-only d#.#
0-07 Password Input d0 to d999 d0
0-08 Password Set d0 to d999 d0
0-09 Memory Mode Selections d0 to d63 d8
Group 1 Basic Parameters
Pr. Explanation Settings
Factory
Setting
NOTE
1-00 Maximum Output Frequency (Fmax) d50.0 to d400 Hz d60.0
1-01 Maximum Voltage Frequency (Fbase) d10.0 to d400 Hz d60.0
230V series: d2.0V to d255V d220
1-02 Maximum Output Voltage (Vmax)
460V series: d4.0V to d510V d440
1-03 Mid-Point Frequency (Fmid) d1.0 to d400 Hz d1.0
1-04 Mid-Point Voltage (Vmid) 230V series: d2.0V to d255V d12