User's Manual
Table Of Contents
- Preface
- Table of Contents
- Chapter 1 Introduction
- 1.1 Receiving and Inspection
- 1.2 Appearances
- 1.3 Installation Steps
- 1.4 Storage
- Chapter 2 Installation and Wiring
- Chapter 3 Start Up
- Chapter 4 Digital Keypad Operation
- Chapter 5 Parameters
- Chapter 6 Fault Code Information
- Chapter 7 Troubleshooting
- 7.1 Over Current (OC)
- 7.2 Ground Fault
- 7.3 Over Voltage (OV)
- 7.4 Low Voltage (Lv)
- 7.5 Over Heat (OH)
- 7.6 Overload
- 7.7 Keypad Display is Abnormal
- 7.8 Phase Loss (PHL)
- 7.9 Motor cannot Run
- 7.10 Motor Speed cannot be Changed
- 7.11 Motor Stalls during Acceleration
- 7.12 The Motor does not Run as Expected
- 7.13 Electromagnetic/Induction Noise
- 7.14 Environmental Condition
- 7.15 Affecting Other Machines
- Chapter 8 Maintenance and Inspections
- Appendix A Specifications
- Appendix B Accessories
- Appendix C How to Select the Right AC Motor Drive
- Appendix D CE

Chapter 5 Parameters|VFD-S Series
5-76 Revision August 2006, SE08, SW V2.61
When this parameter is set to gain =1, PID output is Derivative time. At this time, error value –
error value of the preceding item= additional respond speed and it is easy to have over
compensation situation.
A-05 Upper Bound for Integral Control Unit: 1
Settings d0 to d100% Factory Setting: d100
This parameter determines the Upper Bound for Integral Control while operating in the PID
feedback loop. (Limit = 1-00×A-05 %). During a fast Integration response, it is possible for
the frequency to spike beyond a reasonable point. This parameter will limit this frequency
spike.
A-06
Primary Delay Filter Time
Unit: 2 msec
Settings d0 to d999 Factory Setting: d0
Primary Delay Filter Time will slow down oscillation of the system.
A setting of d0 disables this function.
A-07
PID Output Frequency Limit
Unit: 1
Settings d0 to d110% Factory Setting: d100
This parameter determines the limit of the PID output frequency. If this parameter is set to
110%, then the maximum output frequency while in the PID operation will be (110% x Pr.01-
00) 66Hz.
A-08
Feedback Signal Detection Time
Unit: 0.1
Settings d0.0 to d650 seconds Factory Setting: d0.0
This parameter defines the detection time for the loss of a feedback analog signal. The drive
will follow the operating procedure programmed in Pr.A-09 if the feedback signal is lost for
more than the time set in Pr. A-08.
A setting of 0.0 disables this function.
A-09 Treatment of the Erroneous Feedback Signals
Factory Setting: d0
Settings d0 Warning and RAMP to stop
d1 Warning and COAST to stop