76  PMAC I-Variable Specifiation 
Motor Movement I-Variables 
Ix20  Motor x Jog/Home Acceleration Time 
Range 
0 .. 8,388,607 
Units 
msec 
Default 
0 (so Ix21 controls) 
Remarks 
Ix20 establishes the time spent in acceleration in a jogging, homing, or programmed 
RAPID-mode move (starting, stopping, and changing speeds). However, if Ix21 
(jog/home S-curve time) is greater than half this parameter, the total time spent in 
acceleration will be 2 times Ix21. Therefore, if Ix20 is set to 0, Ix21 alone controls the 
acceleration time in “pure” S-curve form. In addition, if the maximum acceleration rate set 
by these times exceeds what is permitted for the motor (Ix19), the time will be increased so 
that Ix19 is not exceeded. 
Note: 
Do not set both Ix20 and Ix21 to 0 simultaneously, even if you are 
relying on Ix19 to limit your acceleration, or a division-by-zero 
error will occur in the jog move calculations, possibly resulting in 
erratic motion. 
A change in this parameter will not take effect until the next move command. For 
instance, if you wanted a different deceleration time from acceleration time in a jog move, 
you would specify the acceleration time, command the jog, change the deceleration time, 
then command the jog move again (e.g. J), or at least the end of the jog (J). 
See Also 
I-variables I50, Ix16, Ix19, Ix21, Ix22, Ix23, Ix87, Ix88 
Jogging and Homing Moves (Basic Motor Moves) 
RAPID-mode moves (Writing a Motion Program) 
On-line commands HM, J+, J-, J=, J^, J:, J/ 
Motion program command HOME, RAPID 
Ix21  Motor x Jog/Home S-Curve Time 
Range 
0 .. 8,388,607 
Units 
msec 
Default 
50 
Remarks 
Ix21 establishes the time spent in each half of the S for S-curve acceleration in a jogging, 
homing, or RAPID-mode move (starting, stopping, and changing speeds). If this 
parameter is more than half of Ix20, the total acceleration time will be two times Ix21, and 
the acceleration time will be “pure” S-curve (no constant acceleration portion). If the 
maximum acceleration rate set by Ix20 and Ix21 exceeds what is permitted for the motor 
(Ix19), the time will be increased so that Ix19 is not exceeded. 
Note: 
Do not set both Ix20 and Ix21 to 0 simultaneously, even if you are 
relying on Ix19 to limit your acceleration, or a division-by-zero 
error will occur in the jog move calculations, possibly resulting in 
erratic motion. 