Geo Macro Drive MI-Variable Reference 137
MACROSTASCII255 command, the first “unordered” station in the ring will respond.
MI11 can also be set with the ASCII command STN={constant}. The value of MI11 can also be
queried with the ASCII command STN.
MS{node},MI12 Card Identification (Read Only)
Range: 0 – $FFFFFF
Units: none
Default: $
93596 (603542)
This returns the card part number. The same as the CID ASCII command.
MS{node},MI13 Ring Break Output indicator
Range: 0 – $F
Units: none
Default: 0
In case of a ring break error, MI13 controls the Geo MACRO output lines and only as a safety feature.
Choose what the output state would be in a ring break situation, High (12-24V) or Low (GND) for each
individual output, depending on sinking or sourcing setup. Default MI13 equals 0, so in case of ring
break, all outputs are turned off.
Output In Case Of Ring Break Error
Output n is enabled
(True)
MS{node},MI13 - Bit Value
GP OUT n COL* GP OUT n EMT**
0 12-24V 0V
Output 1 1
1 0V 12-24V
0 12-24V 0V
Output 2 2
1 0V 12-24V
0 12-24V 0V
Output 3 3
1 0V 12-24V
0 12-24V 0V
Output 4 4
1 0V 12-24V
*COM EMT (pin10) is wired to GND and pin 9 (COM COL) is let floating
**COM COL (pin 9) is wired to 12-24V and pin 10 (COM EMT) is let floating
Note:
MS{node},MI13 was added in Geo MACRO firmware versions 1.005 and above.