%on-time is the percentage of time the regen circuit is active
Note:
The Turn On voltage for the shunt circuitry for all Geo drives is 388.5V. There is
a Hysteresis of 20V, so if the regen turns on @ 388.5V it will not turn off until it
drops to 367.5V.