Technical data
t +44(0) 121 327 7771 e sales@mwatechnology.com w www.mwatechnology.com t +44(0) 121 327 7771 e sales@mwatechnology.com w www.mwatechnology.com
30 31
Description
M-Bus module 670V
Radio Router module 670W
LonWorks module FTT-10A 670Y
GSM6H module excl external antenna 670Z
M-Bus module with pulse inputs 670020
Radio Router module with pulse inputs - require external supply 670021
Prog data logger RTC 4-20 mA inputs and pulse inputs-require external supply 670022
Lon works module FTT-10A with pulse inputs - require external supply 670024
Description
Set of pocket sensors with 1.5m cable 5.8mm dia 6700000A
Set of pocket sensors with 3.0m cable 5.8mm dia 6700000B
Set of pocket sensors with 5.0m cable 5.8mm dia 6700000C
Set of pocket sensors with 10m cable 5.8mm dia 6700000D
Set of pocket sensors with short probe 1.5m cable 6700000F
Set of pocket sensors with short probe 3.0m cable 6700000G
Description
65mm x ½ sensor pocket,stainless steel for 5.8mm 65-57-324
90mm x ½ sensor pocket,stainless steel for 5.8mm 65-57-327
140mm x ½ sensor pocket,stainless steel for 5.8mm 65-57-314
MWA Code Description
KHC2K15 15mm/½ inch BSP
KHC2K 20 20mm/¾ inch BSP
KHC2K 25 25mm/1" inch BSP
KHC2K 30 30mm/1.¼" inch BSP
Description
Type 67 - Pt500 4 wire with 4 analog outputs
COMMUNICATION MODULES
TEMPERATURE SENSOR SET PT500
SENSOR FITTINGS
ELECTRO MECHANICAL HEAT METER
KAMSTRUP 801 INTEGRATOR ONLY FOR HEAT METERING
l Battery, 230V or 24V powered, with pulsed energy output,
1.5 temperature sensors and 1.5m signal cables & pockets
l Mounting Bracket, standard optical data output
l Pulse value to be advised
lFor monitoring purposes only
lComplete with pulse output
lLithium battery powered
lSensors with 1.5m cable
WATER SAVING SYSTEMS/FLOW METER
SPECIFICATIONS:
lPower requirements: Universal input 100 - 260v AC 50/60Hz 1.5A max
lPulse Meter Input: 24v DC 5mA maximum for reed switch type pulse meter, programmable for 1,10 or 100 LPP
lPSU Output: 24v DC @ 1.1A for powering alarm or solenoid valves
lAlarm Output: Normally open free relay contact rated at 5A resistive load 250v AC / 30v DC
lValve Output: Normally open free relay contact rated at 5A resistive load 250v AC / 30v DC
lLCD display: 2 lines x 16 character with LED backlight
lKeypad: with tactile feedback 0-9 numeric keys plus navigation keys for parameter setting and monitoring
lParameters: Litres input range 1 - 32,767, time input range 10 seconds - 45 hrs, time to alarm range 1 min - 45 hrs
lReal time clock: battery backed (10 year life) Connections: via DIN rail terminals, maximum conductor size
l2.5mm², cable entry via stufng glands
lEnclosure: IP65, steel wall mounting overall dimensions 300 x 200 x 150mm (W x H x D) RAL7035 powder coated
lOverall weight: 4.25Kg
Designed to detect major leaks and help prevent ood
damage caused by leaking pipes and ttings or by
vandalism. The WLDS-10 panel is connected to a pulse water
meter installed at the main intake point of the building and
hence monitors the consumption of water. An alarm output
is activated when a continuous ow of water passes through
the water meter at a ow rate above a preset maximum for
a preset period of time.
A normally open free contact is provided for connection to
a BMS (Building Management System) or to activate a local
beacon/sounder type alarm.
A normally closed free contact is also provided to shut off
the water supply via a solenoid shut off valve if required.
The WDLS-20 has a second pulse water meter installed at
the site boundary and in addition can detect a loss of water
between the site boundary and the main intake point.
Features
lMulti parameters enables efcient monitoring
lHighly versatile, user friendly interfac
lAccepts 1,10,100 L/Pulse meters
lOptional beacon / sounder alarm
lRugged steel enclosure to IP65
lShut off valve and BMS options