Specifications
4421 Tradition Trail ● Plano, Texas 75093 ● 972 -964-2700 ● 800-836-7472 
URL:  www.iscenclosurecooling.com ● Email:  iscinfo@iscsales.com 
SP-ENG-210-100-09 Rev 1.6          8 | P a g e   
CAUTION 
If mounting the air conditioner to the enclosure door, confirm with the enclosure manufacturer that the 
door’s hinges will support the air conditioner’s added weight (see equipment specifications). Insure 
that when the door is fully open that the enclosure will not topple over due to the off-center load. 
Unit Specifications 
The following tables provide electrical and refrigeration specifications for the RZ-01 Series Air 
Conditioners. 
  RZ-01A Series 
  Nominal Capacity Rating: 1,000 BTUH 
  Standard Maximum Ambient: 125°F 
  Unit Weight: 57lbs (120/230VAC) 
Model 
Operating 
Voltage 
Range 
(Volts) 
Inrush 
Current  
(Start 
Up 
Current)  
(Amps) 
Loading 
Current 
(Running 
Current) 
(Amps) 
SCCR  
(Short 
Circuit 
Current 
Rating) 
(Amps) 
Recommended 
Fuse Selection 
(Amps) 
KVA Rating 
(K-Watts) 
Refrigerant 
Type 
Refrigerant 
Amount 
(ounces) 
Low/High 
Unit  
Pressures 
(psi) 
RZ-01A -126 
110-120 
22.69 
3.44 
*2 
12 Amp Class 
CC, CCMR 
Time Delay * 
0.5 
R134a 
12.00 
88 / 178 
RZ-01A -236 
220-240 
13.77 
2.67 
*2 
7 Amp Class 
CC, CCMR 
Time Delay * 
0.6 
R134a 
12.00 
88 / 290 
* Time-delay Fuses with the following electrical characteristics are recommended.  Fast -acting fuses 
are not recommended. 
% of Ampere Rating 
Opening Time 
110 % 
15min Minimum 
125 % 
1hr Maximum 
200 % 
12sec Minimum 
4min Maximum 
*2
  SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel / 
enclosure per UL50 & UL508a to protect the AC unit.  Typically 100KA – 200KA for Time-Delay Fuses. 