Specifications
4421 Tradition Trail ● Plano, Texas 75093 ● 972 -964-2700 ● 800-836-7472 
URL:  www.iscenclosurecooling.com ● Email:  iscinfo@iscsales.com 
SP-ENG-210-100-09 Rev 1.6          5 | P a g e   
Moving the Air Conditioners 
Read this section completely before running or installing your DELTA-T air conditioning equipment.  
Note: You will need to perform a Preliminary Test before mounting the air conditioner. Refer to the 
Preliminary Test section in this manual for instructions on how to run this test. You will also need to 
prepare the enclosure that is to be cooled for mounting in accordance with this manual and the 
template supplied. 
Note: DELTA-T air conditioning equipment must be mounted vertically with a minimum of 3” air space 
for condenser air return and supply. If necessary, equipment may be mounted at up to a 5 degree 
angle (rotary compressors) without damaging the compressor. 
If air conditioner is to be shipped or transported at any time; pack in original packaging and strap to 
pallet to prevent damage. Air conditioner must be kept upright at all times. Air conditioners are not 
designed to be shipped attached to an equipment enclosure. Air conditioners shipped which have 
internal damage due to shipping while attached to enclosures are warranty voided. 
Unit Label 
Each air conditioner has a unit label, be sure to record the data from the label to the template below 
and keep this information in a safe place for warranty and ordering parts. To prevent damage to 
equipment, electrical panel and wiring, and to prevent personal injury, assure that the power source is 
compatible with the equipment before operating. When recharging, refrigeration type and amount 
must be the same as shown on the unit label or air conditioner will not operate properly or may be 
damaged and may result in the warranty voided and UL listing voided. 