Specifications
4421 Tradition Trail ● Plano, Texas 75093 ● 972 -964-2700 ● 800-836-7472 
URL:  www.iscenclosurecooling.com ● Email:  iscinfo@iscsales.com 
SP-ENG-210-100-09 Rev 1.6          20 | P a g e   
  *3Note: Refer to Electrical Schematics for further diagnostics.  
Flashing Error 
Codes 
Single or 
Multiple 
Codes? 
2 + 
1 
Refer to Alarm Signals 
in Digital Temperature 
Controller 
Programming Section 
P1 / P2 
combination 
flashing? 
YES 
NO 
Potential bad 
connection. Check 
green connector 
behind controller. 
CA 
YES 
NO 
Check Low Pressure 
Switch Connections 
and Verify Pressure 
switch is closed.  Use 
meter.
3 
P1 or 
P2 
NO 
YES 
Check probe 
connections, potential 
faulty probe. 
LA, LA2, HA, 
HA2 
YES 
Refer to Alarm Signals 
in Digital Temperature 
Controller 
Programming Section 
Fuse / Circuit 
Protection 
Nuisance Trip 
Is fuse opening as 
soon as unit turns 
on? 
NO 
YES 
Check incoming power 
supply and connections 
for potential short circuit 
Does fuse open 
when compressor 
starts? 
YES 
NO 
Check electrical specification. 
Verify proper recommended fuse 
has been selected.  
Check compressor, if excess heat present compressor may 
be faulty.  Contact Technical Support. 