Specifications
4421 Tradition Trail ● Plano, Texas 75093 ● 972 -964-2700 ● 800-836-7472 
URL:  www.iscenclosurecooling.com ● Email:  iscinfo@iscsales.com 
SP-ENG-210-100-09 Rev 1.6          18 | P a g e   
Troubleshooting Guide 
The following guide provides a flow chart to identify a problem, determine the root cause and identify 
the action needed to correct an issue. 
Unit Will Not Run 
Is Unit 
Connected?  
YES 
 NO 
Please Connect 
Power Cord 
Verify Power On/Off 
Switch is on position 
ON 
 OFF 
Toggle Switch 
then Retry 
Verify input power 
meets voltage 
requirements as 
shown in the UL label 
 YES 
If problem is still present contact 
technical support 
Unit Overheats / 
Insufficient Cooling 
Is Filter 
Clean? 
 NO 
Clean / Replace 
Filter 
YES 
Are Condenser & 
Evaporator Fans ON? 
 NO 
Check for Faulty 
Fan & replace 
YES 
Is Condenser 
Coil dirty? 
 YES 
Clean Coil 
 NO 
 NO 
Is Evaporator Coil 
Frozen / Iced? 
 YES 
Potential Bad 
Evaporator Fan, 
check for faulty 
fan. 
 NO 
Contact Qualified Refrigeration Service 
Technician to check Refrigerant Pressure.  Unit 
may have a refrigeration leak.  If problem is not 
resolved contact technical support.  