Instructions

HD32.3 - 33 - V1.4
PMV Index
NOTES
Log number: 1
Number of logging sections
========================
ISO 7243 PMV Index
Reference rules
========================
Model HD32.3 WBGT – PMV
Instrument model
Firm.Ver.=01.00
Version of the instrument firmware
Firm.Date=2008/12/05
Date of the instrument firmware
SN=12345678
Instrument serial number
ID=0000000000000000
Identification code
------------------------
Probe ch.1 description
Description of the probe connected to the inlet 1
Type: Hot wire
Data cal.:2008/10/01
Serial N.:08109450
------------------------
Probe ch.2 description
Description of the probe connected to the inlet 2
Type: Pt100 Tg 50
Data cal.:2008/10/01
Serial N.:08109452
------------------------
Probe ch.3 description
Description of the probe connected to the inlet 3
Type: RH
Data cal.:2008/10/01
Serial N.:08109454
========================
From=2008/11/21 15:00:00
Logging start day and hour
To =2008/11/21 16:30:00
Logging end day and hour
Tot. rec.= 000360
Number of samples acquired by the instrument
MET 1.20
Metabolic rate
CLO 1.00
Cloth resistance
** max value **
Maximum value of the acquired data
Va 0.00 m/s
Air speed
Tg 22.0 °C
Globe Thermometer temperature
Ta 22.0 °C
Wet bulb temperature
RH 39.1 %
Relative humidity
PMV 0.10
PMV – Predicted Mean Vote
PPD 5.10 %
PPD – Predicted Percentage of Dissatisfied
** min value **
Minimum value of the acquired data
Va 0.00 m/s
Air speed
Tg 22.0 °C
Globe Thermometer temperature
Ta 22.0 °C
Wet bulb temperature
RH 39.1 %
Relative humidity
PMV 0.10
PMV – Predicted Mean Vote
PPD 5.10 %
PPD – Predicted Percentage of Dissatisfied
** avg value **
Medium value of the acquired data
Va 0.00 m/s
Air speed
Tg 22.0 °C
Globe Thermometer temperature
Ta 22.0 °C
Wet bulb temperature
RH 39.1 %
Relative humidity
PMV 0.10
PMV – Predicted Mean Vote
PPD 5.10 %
PPD – Predicted Percentage of Dissatisfied
========================
Notes:
========================
NOTE: The printing of a logging section on HD40.1 printer contains only the statistic data. To
visualize all the acquired data, it’s necessary to download the data using DeltaLog10 software.