Installation manual

18 Operation and installation manual SOLIVIA Gateway M1 G2
10.5.1 Power Management
1)
There are four binary inputs that control the maximum power the inverter may feed into
the grid.
Power management is at 100 % for all relay state combination except 60 % for relay 1,
30 % for relay 2, and 0 % for relay 3 (default settings).
10.5.2 Power Factor Control
1)
The power factor conguration page allows the denition of 15 values for the cos φ,
either inductive or capacitive. If all inputs are inactive the cos φ is 1.00.
The values are entered in the form 0.xx, e.g. 0.95 and a checkbox decides whether it is
leading current (capacitive) or not.
NOTICE
Please remember to save the congurations by pressing the “Submit” button.
1) This chapter is only relevant for countries, in which your public grid supplier requires a power reduction
(power management), power factor control and/or power balancing.