17Operation and installation manual SOLIVIA Gateway M1 G2
10.4.4 Force Gateway Reset
To reset the gateway to production settings press either the reset switch for more than
5 seconds or click on the "Reset" button. After reset of the gateway, the default values
shall become used again requiring a new conguration if needed.
All the inverter data are cleared, the device is reset and a new RS485 bus
scan starts, ending with a ash store. The settings of Power Balancing,
Power Management, Power Factor Control, Baud-rate and send interval
remain unchanged.
10.4.5 Restart Gateway
By pressing the "Restart" button the gateway will be restarted. This restart has no
impact on any congurations set before.
10.5 Digital Inputs
The SOLIVIA gateway gives a voltage to the output A and measures the inputs 1 to 8.
In this way the SOLIVIA gateway can detect the state of the relays of the ripple control
receivers. The information which relay shall control what parameter has to be communi-
cated by the public grid supplier.
Example: Information from the public grid supplier: If relay 2 is closed then the power
factor (cos ϕ) shall be set to 0.93 capacitive, if relays 1 and 2 are closed then the power
factor shall be set to 0.98 inductive.
If the reactive power control receiver is connected to the SOLIVIA gateway as shown
in gure 3 (Chapter 7.5) then the “Power Factor Control” should be congured like in
gure 5.