10.4.4 Force Gateway Reset
To reset the gateway to production settings press either the reset switch for more than
5 seconds or click on the "Reset" button. After reset of the gateway, the default values
shall become used again requiring a new conguration if needed.
All the inverter data are cleared, the device is reset and a new RS485 bus
scan starts, ending with a ash store. The settings of Power Balancing,
Power Management, Power Factor Control, Baud-rate and send interval
remain unchanged.
10.4.5 Restart Gateway
By pressing the "Restart" button the gateway will be restarted. This restart has no
impact on any congurations set before.
10.5 Digital Inputs
The SOLIVIA gateway gives a voltage to the output A and measures the inputs 1 to 8.
In this way the SOLIVIA gateway can detect the state of the relays of the ripple control
receivers. The information which relay shall control what parameter has to be communi-
cated by the public grid supplier.
Example: Information from the public grid supplier: If relay 2 is closed then the power
factor (cos ϕ) shall be set to 0.93 capacitive, if relays 1 and 2 are closed then the power
factor shall be set to 0.98 inductive.
If the reactive power control receiver is connected to the SOLIVIA gateway as shown
in gure 3 (Chapter 7.5) then the “Power Factor Control” should be congured like in
gure 5.