11. Saving and Loading Data and Settings
Operation and Installation Manual for SOLIVIA 2.0/2.5/3.0/3.3/3.6/5.0 EU G4 TR
66
11.5 Loading Settings
To simplify the setup procedure, the settings from another solar
inverter of the same type can be loaded and used in another solar
inverter for use with the same settings. Information on saving the
settings can be found in “11.4 Saving Settings”, p. 65.
USB features
Options
Install settings
-------------------
Production info
SOLIVIA ##
1. In the main menu, press the buttons to select USB
features and then press the
button.
A note on IP65 protection is then displayed.
protection.
will lose the IP65
Without cover, you
2. Press the button to conrm.
The 300 USB features menu is then displayed.
Save settings
Save swap data
Create reports
Load settings
Service
300 USB features
3. Press the buttons to select Load Settings and
then press the
button.
The solar inverter searches for available les on the
USB drive.
When les are found, the Select RS485 ID menu is
displayed.
NOTE: The STUP_###.CFG le must
be in the main directory of the USB
drive. The ### characters represent
the RS485 ID of the solar inverter
from which the data is to be loaded,
for example "001".
NOTE: If the message Pendrive
error is displayed, make sure the
USB drive is properly inserted.
NOTE: If the message No les
found is displayed, make sure the
les are in the main directory of the
USB drive.
ID: 1
Select RS485 ID
4. Press the buttons to select the ID and then press
the
button.
The data is then loaded.
A message is displayed when the loading process is
successful.
Press ENTER
Successful
Load data
5. Press the button to conrm.