Installation manual

10. Settings
Operation and Installation Manual for SOLIVIA 2.0/2.5/3.0/3.3/3.6/5.0 EU G4 TR
60
10.10.3 ConstantPowerFactorcosφ
Menu 520 Reactive PwCtrl
Description
Allows a constant cos φ power factor to be congured.
Accessing the Menu
Main Menu > User Settings > Reactive PwCtrl
USB features
Options
Production info
User settings
Diagnostic&Alarm
SOLIVIA ##
1. In the main menu, press the
buttons to select User
Settings and then press the
button.
for assistance.
Ask your installer
energy production.
Changes could affect
2. Press the button to conrm.
-------------------
Reactive PwCtrl
Active PwCtrl
-------------------
500 User settings
3. Press the buttons to se-
lect Reactive PwCtrl and then
press the
button.
Cos phi: ind 1.00
Mode: Fix. cosPhi
-------------------
520 Reactive PwCtrl
4. Press the buttons to
select Mode and then press
the
button.
Cos phi: ind 1.00
Mode: Fix. cosPhi
-------------------
520 Reactive PwCtrl
5. Press the buttons to set
Mode to Cos phi (P) and then
press the
button.
-------------------
Cos phi: ind 1.00
Mode: Fix. cosPhi
-------------------
520 Reactive PwCtrl
6. Press the buttons to
select the parameter Cos Phi.
Press the
button to change
the value.
CongurableParameters
Display Text Designation Description
Cos Phi
cos φ Denes cos φ to be the set
value.
inductive | capacitive
1 - 0.8
10.11 Local Control (Italy only)
NOTE
This function is only available for the IT BT 21
grid.
Menu 500 User Settings
Description
In accordance with CEI 0-21:2012-06, the integrated grid and sys-
tem protection (SPI) can be activated or deactivated for PV sys-
tems equal to or lower than 6 kW.
Accessing the Menu
Main Menu > Options > Grounding
USB features
Options
Production info
User settings
Diagnostic&Alarm
SOLIVIA ##
1. In the main menu, press the
buttons to select User
Settings and then press the
button.
-------------------
Local control: Off
-------------------
500 User settings
2. To change the setting, press
the
button and then change
the value using the
buttons.
CongurableParameters
Display Text Designation Description
Local control
Local control On | Off
On = Parameter as per
CEI 0-21:2012-06 Sect. 8.6
NOTE
The parameters that must be congured under
CEI 0-21:2012-06 can be changed using the
Delta service software.