Operation and Installation Manual for SOLIVIA 2.0/2.5/3.0/3.3/3.6/5.0 EU G4 TR
10. Settings
EN
Example
The parameters for points A to D are congured in this example as
follows:
Display Text Description
A cos phi: ind 1.00
Point A: cos φ is set to inductive
1.00. Since cos φ = 1.00, capacitive
could also be congured.
The power ratio P/Pn is automatically
set to 0% and cannot be changed.
B cos phi: ind 0.95
Point B: cos φ is set to inductive
1.00.
B P/Pn ratio: 23%
Point B: Power ratio P/Pn is set to
23 %.
C cos phi: cap 0.90
Point C: cos φ is set to capacitive
1.00.
C P/Pn ratio: 75%
Point C: Power ratio P/Pn is set to
75 %.
D cos phi: cap 0.95
Point D: cos φ is set to inductive
0.95.
The power ratio P/Pn is automatically
set to 100 % and cannot be changed.
This results in the following behavior from the solar inverter,
depending on the current fed active power:
Power ratio P/P
n
0 % 50 % 100 %
1
0.8
0.8
Point A
Point B
Point C
Point D
cos φ
inductive
capacitive
Fig. 10.4: Example of conguring cos φ (P) function
When changing the currently fed active power, the cos φ runs along
the plotted line.
EffectsofActivePowerLimitationonBehaviorof"cosφ(P)"
Function
If active power limitation is congured during commissioning and/or
through the "power reduction" function, the behavior of the "cos φ
(P)" function changes.
Power ratio P/P
n
0 % 50 % 100 %80 %
1
0.8
0.8
Point A
Point B
Point C
Point D
cos φ
inductive
capacitive
5 kW4 kW2.5 kW
Example: SOLIVIA 5.0 EU G4 TR, limited to 4 kW
Fig. 10.5: Effect of active power limitation on the "cos φ (P)"
function
This active power reduction to 4 kW means point D can never be
achieved. This applies for the entire grey area.
Accessing the Menu
Main Menu > User Settings > Reactive PwCtrl
➔
USB features
Options
Production info
User settings
Diagnostic&Alarm
SOLIVIA ##
1. In the main menu, press the
buttons to select User
Settings and then press the
button.
for assistance.
Ask your installer
energy production.
Changes could affect
2. Press the button to conrm.
➔
-------------------
Reactive PwCtrl
Active PwCtrl
-------------------
500
User settings
3. Press the buttons to se-
lect Reactive PwCtrl and then
press the
button.
➔
A Cos phi: ind 1.00
Mode: Cos phi(P)
-------------------
520 Reactive PwCtrl
4. Press the buttons to
select Mode and then press
the
button.
➔
A Cos phi: ind 1.00
Mode: Cos phi(P)
-------------------
520 Reactive PwCtrl
5. Press the buttons to set
Mode to Cos phi (P) and then
press the
button.
6. Select a parameter with the
buttons. Press the but-
ton to change the value.
CongurableParameters
(see Fig. 10.3, S. 58)
Display Text Designation Description
A cos phi: ind
1.00
Point A: cos φ inductive 0.8 - 1.0 or
capacitive 0.8 - 1.0
B cos phi: ind
1.00
Point A: cos φ inductive 0.8 - 1.0 or
capacitive 0.8 - 1.0
B P/Pn ratio:
Point B: Power ratio
P/P
n
1 - 49 %
C cos phi: ind
1.00
Point C: cos φ inductive 0.8 - 1.0 or
capacitive 0.8 - 1.0
C P/Pn ratio:
Point C: Power
ratio P/P
n
50 - 99 %
D cos phi: ind
1.00
Point D: cos φ inductive 0.8 - 1.0 or
capacitive 0.8 - 1.0