Installation manual

57
Operation and Installation Manual for SOLIVIA 2.0/2.5/3.0/3.3/3.6/5.0 EU G4 TR
10. Settings
EN
10.9.3 Active Power by Frequency P(f)
Menu 512 Power/Frequency
Description
Allows the statistics to be reset. The currency and credit per kWh
can also be congured.
This function alters the fed active power depending on the grid
frequency. If a starting frequency is exceeded, the fed active power
is limited. If a stopping frequency is exceeded, the active power is
no longer fed.
Behavior as per VDE AR N 4105 is described below.
Variant 1: The grid frequency alters between f
Start
and f
Stop
.
P
m
f (Hz)
f
start
f
stop
Gradient (%/Hz)
Fig. 10.1: Function P(f), variant 1
Once the grid frequency exceeds the value f
Start
, the value of the
active power P
m
being fed at this moment is automatically saved
and active power limiting is activated.
As long as the grid frequency stays above f
Start
and under f
Stop
, the
fed active power value runs along the gradients: Active power drops
with increasing grid frequency and increases with decreasing grid
frequency.
Variant 2: The grid frequency exceeds f
Stop
.
P
m
f (Hz)
f
start
f
stop
Gradient (%/Hz)
Fig. 10.2: Function P(f), variant 2
When the grid frequency exceeds f
Start
but then remains under f
Stop
,
the solar inverter behaves as described in variant 1.
However, as soon as the grid frequency exceeds f
Stop
, the active
power feed is stopped.
Active power feed will resume once the grid frequency falls below
f
Start
. Once resumed, the active power will increase by 10% per
minute.
Accessing the Menu
Main Menu > User Settings > Active PwCtrl > Power vs freq
USB features
Options
Production info
User settings
Diagnostic&Alarm
SOLIVIA ##
1. In the main menu, press the
buttons to select User
Settings and then press the
button.
for assistance.
Ask your installer
energy production.
Changes could affect
2. Press the button to conrm.
Reactive PwCtrl
Active PwCtrl
-------------------
500
User settings
3. Press the buttons to
select Active PwCtrl and then
press the
button.
-------------------
Power vs freq
Power reduction
-------------------
510 Active PwCtrl
4. Press the buttons to
select Power vs freq and then
press the
button.
Stop freq: 51.50Hz
Start freq: 50.20Hz
-------------------
512 Power vs freq
5. Select a parameter with the
buttons. Press the but-
ton to change the value.
CongurableParameters
Display Text Designation Description
Start freq
Start frequency Frequency at which the
feeding of active power is
limited.
Value range: 50.00
- 65.00 Hz
Standard: 50.20 Hz
Stop freq
Stop frequency Frequency at which the
feeding of active power is
stopped.
Value range: 50.00
- 65.00 Hz
Standard: 51.50 Hz
Gradient
Gradient Adjustment of the fed
active power in percent
per Hz.
Value range: 0 - 150 %
Standard: 40 %