Installation manual

41
Operation and Installation Manual for SOLIVIA 2.0/2.5/3.0/3.3/3.6/5.0 EU G4 TR
8. Commissioning
EN
8.5 Commissioning in Italy for PV Systems Below 6 kW
The standard commissioning is valid for the following countries and grids.
Country Grid Notes
Italy
IT BT 21
As per CEI 0-21:2012-06 for PV sys-
tems equal to or less than 6 kW.
1. Check all connections and cables for damage and correct
seating. Correct the installation if necessary.
DC DISCONNECT
OFF
ON
2. Switch on the DC isolating switch.
The startup process of the solar inverter will begin.
After the startup process and the automatic self-test,
the commissioning procedure of the inverter starts
and the Installation menu is displayed.
continue
Language: English
-------------------
Installation
3. To change the language, press the button and then
set the language using the
buttons. Press the
button to apply the language.
Available languages:
Czech | Danish | Dutch | English |
French | German | Italian | Polish |
Portuguese | Romanian | Slovak |
Slovenian | Spanish
-------------------
continue
Language: English
-------------------
Installation
4. Press the buttons to select continue and then
press the
button.
This displays the Load USB Data menu.
-------------------
No
Yes
-------------------
Load USB data
5. Press the buttons to select No and then press the
button.
The Grid Selection menu is displayed.
continue
Grid: IT BT 21
-------------------
Grid selection
6. To change the grid, press the button and then set the
grid to IT BT 21 using the
buttons. Press the
button to apply the grid.
NOTE: Here you can select the proper
grid for your country.
-------------------
continue
Grid: IT BT 21
-------------------
Grid selection
7. Press the buttons to select continue and then
press the
button.
The Local Control menu is then displayed.
continue
Local control: Off
-------------------
Local control
8. To change the settings, press the button and then set
the option using the
buttons. Press the button
to apply the setting.
-------------------
continue
Local control: Off
-------------------
Local control
9. Press the buttons to select continue and then
press the
button.
The Locked Power Limit menu is displayed.